The ThermElect Hydronic system should be plumbed with a primary loop and secondary (zone) loops. The

primary loop needs to consist of a minimum of 12' of 1.25" pipe. The heat exchanger inlet and outlet are 1.5"

diameter, reducers will be required if 1.25" pipe is elected for the primary loop. The secondary (zone) loops re-

quire additional pump(s) to operate effectively. Refer to Typical Primary Loop and the Typical System Plumbing

Diagrams below for installation information.

The primary loop serves to regulate heat transfer from the system’s heat exchanger. The primary loop pump

should be powered by ThermElect Hydronic control system as shown in Figure 11. If using other control meth-

od, flow MUST continue for at least 30 seconds at the end of a heat call.

TyPICaL PRIMaRy LOOP

FIgURE 11

air Vent

air Separator

1

Expansion

Tank

Pressure

Relief Valve

(factory Supplied)

Optional

Temperature and

Pressure Relief Valve

(consult local code)

Inlet

Outlet

*Primary

Loop

Pump

Piping MUST

Be Supported

Zone

Connection

area

Primary Loop Pump

Control Wiring

T

herm

e

lecT

h

ydronic

i

nSTallaTion

3.11

i

nSTallaTion

3.10

T

herm

e

lecT

h

ydronic

TyPICaL SySTEM PLUMBINg SINgLE TEMPERaTURE ZONES

FIgURE 12

Single Temperature Zone

NOTE: There are many additional ways to connect plumbing and regulate temperature from the primary loop onward.

White

Red

Primary Loop

Secondary Loop

Primary

Loop Pump

ThermElect

Hydronic

Exchanger

This Valve Must

Be Open during

Normal Operation

White

Red

Primary Loop

Secondary Loop

This manual is related to the following products: