VENT HOOD TERMINATION CLEARANCES FOR U.S. INSTALLATIONS

The SS2 has been ETL Listed according to the requirements of the National Fire Protection Association #31, and #211 as follows
below, (See Diagram A).

• The exit terminals of mechanical draft systems shall not be less than 7 feet above grade when located adjacent to public walkways.

• A venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.

• The venting system shall terminate at least 4 feet below, 4 feet horizontally from or 1 foot above any door, window or gravity air

inlet into any building.

• The bottom of the vent terminal shall be located at least 12 inches above grade.

• The exit terminal shall be so arranged that the flue gases are not directed so as to jeopardize people, overheat combustible

structures or enter buildings.

• Not to be less than 10 feet from an adjacent building.

The SS2 is also Listed to terminate a minimum of 12” below, above or horizontally from a soffit, deck or adjacent sidewall.

CAUTION: The owner of the SS2 must keep the area around the vent terminal free of snow, ice and debris.

It is not recommended for the SS2 to be terminated on a wall that faces the direction of the prevailing winds.
Backdrafts by severe winds can cause oil odors to remain in the structure and/or interrupt equipment operation.