SPECIFICATIONS
Motor: 115/1/60, 3000 RPM, 1/25 HP, 1.6 FLA, Ball Bearing Permanently Lubricated.
Fan Proving Switch: Non-adjustable set point of -.40” W.C. on pressure drop. Contacts rated for an inductive load of 6.2 FLA.
High Limit: Manual reset N/C contacts, open at 170oF + 8oF (77oC + 5oC). Contacts rated at 10 FLA at 120 VAC.
Post-Purge Timer: Adjustable from 1 to 10 minutes. Dual voltage, non-polarity sensitive input (24-120 VAC).
Cooling Fan: 115/1/60, RPM 3000-3300, AMPS .2, CFM 105, DB Level 50.
2
GENERAL INFORMATION
Each SS2 is electrically factory line tested before shipment.
After opening carton, inspect thoroughly for hidden damage. Impeller should rotate freely. If any damage is found notify freight
carrier and your distributor immediately and file a concealed damage claim.
INSTALLATION RESTRICTIONS
1. The SS2 may not be installed on condensing type or solid fuel burning appliances, incinerators or incinerating toilets.
2. The SS2 may only be installed on Flame Retention Head Burners.
3. The SS2 may only be installed on appliances equipped with a barometric draft control.
4. The SS2 may not be connected to a natural draft chimney.
5. The SS2 shall not be installed where flue gas temperatures exceed 650oF (343oC) at its inlet. Flue gas temperature verification:
A) Verify flue gas temperature at appliance inlet is at or above 250oF (121oC) after 5 minutes of operation during setup. See
“Draft Adjustment Procedure” on page 12, step 9.
AND
B) After 15 minutes of operation, measure flue gas temperature to verify it is not more than 650oF (343oC) at SS2 inlet.
6. The electrical load controlled through the Fan Proving Switch must not exceed its nameplate ratings.
7. Vent runs of over 15 linear feet (4.5 meters) require the use of an approved, insulated vent connector to prevent problems related
to condensation.
Improper installation, adjustment, alterations, service or maintenance can cause injury, property damage or death. Refer to this
manual. For assistance or additional information consult a qualified installer, service agency or the equipment supplier.
Do not exceed the recommended input range of the SS2. Under no circumstances shall the minimum draft adjustment be used for
the larger input range of this product. Improper adjustment may result in the dispersion of flue products (carbon monoxide) into
the building interior causing carbon monoxide poisoning or death.