Tjernlund SS2 SideShot (Discontinued Version - Pre UC1 Universal Control) 8504063 Rev B 11/99 User Manual
Page 15
14
TROUBLESHOOTING ELECTRICAL PROBLEMS
NOTE: When 120 VAC is applied to terminals L1 and L2 of the SS2 terminal strip, the SS2 may start up and run for 1 to 10
minutes. Do not initiate a call for heat with the appliance until the SS2 is finished with it’s post purge time cycle.
The following guide is intended to be used if a problem occurs during
the use of the SS2 side wall vent system. At several steps through-
out the guide you will be required to measure 115 Volts with a volt-
meter, (See Diagram L).
Extreme caution must be exercised to prevent injury. If you are
unable to determine the defective part with the use of this guide, call
your Tjernlund distributor or Tjernlund Products direct at
1-800-255-4208 for further assistance.
DIAGRAM L
Remove the external control wire attached to terminal
"O" of the SS2 terminal strip. This should cause
the motor to shut down within ten minutes (after the
post-purge cycle has finished).
SS2 and appliance are not interlocked correctly.
Voltage is present at terminal "O" constantly. Voltage
should cycle on/off with appliance cycles. Refer to
electrical diagrams in this manual. Rewire according
to appropriate diagram.
Replace Relay/Timer,
Part # 950-1067.
No
Yes
SYMPTOM 1: SS2 MOTOR RUNS CONTINUOUSLY
Step 1.
Verify that 115V is present between "L1" and "L2"
on SS2 terminal strip, (See Diagram L).
Check circuit breaker or fuse
and electrical connections.
SideShot and appliance are not interlocked correctly
or malfunction of appliance controls. Refer to
electrical diagrams in this manual and appliance
manufacturer's troubleshooting guide.
Replace Relay/Timer,
Part # 950-1067.
No
No
No
Yes
Yes
Yes
SYMPTOM 2: SS2 MOTOR WILL NOT OPERATE
Replace Motor, Part # 950-0015.
Step 2.
With thermostat calling for heat, check for voltage
between "O" and "R" of SS2 terminal strip.
Step 3.
Verify that 115V is present between "M" and "L2"
on Relay/Timer.