4 setpoint outputs, Example 1, Example 2 – Rice Lake Counting Scales - IQ6500 Installation and Operation Manual User Manual
Page 34: Example 3

31
9.4
Setpoint Outputs
Two setpoint outputs are available as open-collector transistor transistor logic (TTL) level outputs for driving
relays on the RS-232 option. The outputs are available on the circular connector on the rear of the scale
marked “setpoint” and are configured by setting SPEC15 bit 2 and SPEC16 bits 0–3. See Section 6.0 for more
information about configuring SPEC codes.
Pin Number
Signal
2
GND
3
SP1
4
SP2
Others
Not used
The following figure shows the minimum and maximum levels of the two setpoint outputs, SP1 and SP2.
The following figures provide examples of using the setpoint outputs.
8
6
1
4
2
5
3
7
(H)
(L)
(H)
(L)
... 5 volts
... 5 volts
Min.
Max.
SP1
Output
SP2
Output
◆
◆
◆
◆
off
900
1000
BUZZER
SP1
Output
SP2
Output
beeping on
intermittently
buzzer on
continuously
Example 1
•
Example 1 uses a standard quantity setpoint
of 1000 pieces (SP2) with a percentage pre-
alarm of 90 percent or 900 pieces (SP1).
SPEC16 must be set at 0000.
off
400
500
SP1
Output
SP2
Output
BUZZER
beeping on
intermittently
buzzer off
Example 2
•
Example 2 uses an over/under quantity
arrangement where SP1 is 500 pieces and
SP2 is 400 pieces. SPEC16 must be set at
0100.
Example 3
•
Example 3 uses an alarm set for 120 percent
(SP2) of 1000 pieces (SP1). SPEC16 must
be set at 0000.
off
1000
1200
SP1
Output
SP2
Output
beeping on
intermittently
buzzer on
continuously