beautypg.com

ETS-Lindgren 2187 Turntable User Manual

Page 22

background image

22

| Assembly

and

Installation

4. Once tension is placed on all three wrenches, drill a 5/32-in hole through

the counter-sunk holes in the floor flange. Drill completely through the

panel and place screws into the holes.

5. Continue working around the floor flange, completing two or three holes

at a time.

Make sure that a 1/4-in gap between the turntable top and the mounted brush

ring be held as close as possible so that the grounding brushes seat properly.

Also, make sure the flange ends are flush with each other.

6. Continue mounting until all screws are installed. Some screws may fall

between the floor panel joints. Try to position the flanges, making sure as

few screws hit these points as possible, and making sure that the first or

last hole in the flange is not too close to one of these joints. Trim the top

floor joint strips to fit up against the flange.

Floor Flange Installation in a Concrete Pit

Installing in a concrete pit is the same as a paneled floor, with the exception of

the mounting hardware. Instead of the #14 x 1-in square socket flat head screws,

use 1/4 x 1.75-in Phillips flat head concrete anchors.

These tools are required for the next stage of installation:

• 1/2-in hammer drill

• 3/16 x 3.5-in hammer drill bit, at minimum

• Vacuum to clean inside the drilled holes for maximum thread

engagement

When drilling holes, be aware of buried conduit and pit drainpipes. Drill 3/16-in

holes, two inches minimum depth.