beautypg.com

Cyclades PM IPDU User Manual

Page 57

background image

Chapter 4: Command Line Interface

45

Examples

To check the hardware overcurrent status of IPDU #1, enter the following.

To reset the hardware overcurrent protection, enter the following.

id

The id command sets or displays the ID of a PM IPDU. A maximum of 16 characters (not case
sensitive) is allowed. Spaces, numbers, and special characters are allowed. This command is
available to the administrator user only.

This command works in a daisy chain.

Syntax

id [] []

-or-

id [] []

-or-

id

Arguments

IPDU

number in a daisy chain

Identification string previously set by the id command

If follows , or if the parameter is typed twice, the latest entry of
the parameter updates the ID string.

no argument

Displays the IDs of all PM IPDUs in the daisy chain

Examples

To set the ID of PM IPDU 1 R&D, enter the following.

pm>hwocp 1

IPDU #1: HW overcurrent protection is OFF.

pm>hwocp 1 reset

IPDU #1 was reset

pm>id 1 R&D

IPDU #1: id = R&D