Alarm, Assign – Cyclades PM IPDU User Manual
Page 46

34
Cyclades PM IPDU Installer/Administrator/User Guide
alarm
The alarm command sets and reads the current threshold. This command is available to the admin
user only.
Syntax
alarm | [
Arguments
IPDU
number in a daisy chain
Identification string previously set by the id command.
The current threshold is the maximum allowed current on the power strip
no argument
Displays alarm status of all PM IPDUs in the daisy chain
Examples
To set the threshold, enter the following.
To read the threshold, enter the following.
assign
The assign command assigns an outlet to a given user. The user is then be able to manage such
outlets. This command is available to the admin user only.
Syntax
assign
Arguments
Outlet number, such as “5”, outlet name such as “sunfire”, or group of outlets
such as “1, 3-5”
Desired username
pm>alarm 1 5.6
Setting alarm threshold on IPDU #1 to 5.6A
pm>alarm 2 7.8
Setting alarm threshold on IPDU #2 to 7.8A
pm>alarm
Alarm threshold on IPDU #1 is 5.6A
Alarm threshold on IPDU #2 is 7.8A