Confi guration of FlexBar 3431
FlexBar 3431
Profi bus PA
FlexProgrammer
Engineering units for the display (optional)
x
Enable/disable the address button at the display
x
Enable/disable the display function
x
Device address setting (if display mounted/enabled)
x
x
x
Engineering units for Profi bus PA output
x
TAG
x
x
Zero point calibration
x
2-point calibration
x
Factory settings
x
Measuring limits and ranges
x
Scaling
x
Warning and Alarm limits
x
Damping
x
Output limits and engineering unit
x
Linearisation table
x
Confi guration - Overview
Unless specifi ed the FlexBar 3431 will be confi gured with device
address 126.
FlexBar 3431 can be confi gured either online via the Profi bus
®
PA
network or offl ine with the dedicated Baumer FlexProgrammer unit
connected to a standard PC.
The following parameters can be confi gured using the FlexProgrammer:
Proces Value Scale corresponding to 0...100% output at the display.
Enable/Disable the push button at the display.
Set the transmitter device address.
Set/change the display engineering unit.
In a Profi bus
®
PA network all standard parameters for a PA pressure
device, such as measuring limits, linearisation, damping, one- or two
points calibration, alarm limits, etc. can be confi gured.
Confi guration
Setting the device address
The push button at rear of the display is for control and setting of the
transmitter device address.
Monitor the address:
Push the button once.
Change the address: Push the button in 5 secs., the display fl ashes.
Increase address by 1: Push the button again.
Increase address by >1: Push and hold the button.
No activity for 5 secs.: The display shows the process value and the
new address has been activated.
The push button can be enabled/disabled using the FlexProgrammer
Confi guring with FlexProgrammer
WARNING:
Disconnect the Profi bus PA wires before connecting
the FlexProgrammer to FlexBar 3431.
FlexProgrammer
1
2
Note: Ambient temperature range 0...50°C
FlexProgrammer
FlexProgrammer 9701
1
2
Red clip
Black clip