4.5. Specific commands

command

code

data length

in bytes

read

write

Broad-

cast

saved in

EEPROM

functionality

K (4Bh)

-

-

X

X

X

Specific command: Clear profile (delete)

Q (51h)

1

-

X

X

X

Specific command: N 143 reset

X (58h)

2 / 4 / 8

X

-

-

-

Specific command: read device data


4.5.1. Clear profiles „K“ (4Bh)

This command will perform a collective deletion of all previously saved profiles.

Example 1: Clear profiles of a specific N 143

SOH Adr Cmd Data EOT CRC

Transmission

01h 20h 4Bh 7Fh 04h C6h

SOH Adr Data EOT CRC

Response

01h 20h 6Fh 04h 52h


N 143 replies by standard response ‚o’ (6Fh) = OK


Example 2: Clear profiles in all positioning displays by broadcast command (Adr = 99)

SOH Adr Cmd Data EOT CRC

Transmission

01h 83h 4Bh 7Fh 04h DBh

Response

Not confirmed

Important: A profile reset operation will set all profile data to FFFFFFhex and the current profile number to
FFhex. In the display will appear 6 hyphens instead of the target.

4.5.2. N 143 reset „Q“ (51h)

This command will restore default in specific parameters, either individually or collectively.

Data = p (70h) = Reset digiset offset

Data = q (71h) = Restore default

Data = t (74h) = Restore 98 as device address.

Data = x (78h) = Multiturn counter is set to 4096 which corresponds to 0.

Data = ∆ (7Fh) = Execute all above functionalities .

Note: No profile reset. Please utilize command „R“ for a profile reset operation

Example 1: Restore default in a specific positioning display

SOH Adr Cmd Data EOT CRC

Transmission

01h 20h 51h 7Fh 04h AEh

SOH Adr Data EOT CRC

Response

01h 20h 6Fh 04h 52h


N 143 replies by standard response ‚o’ (6Fh) = OK


Example 2: Restore default in all positioning displays by broadcast command (adr = 99)

SOH Adr Cmd Data EOT CRC

Transmission

01h 83h 51h 7Fh 04h B3

Response

Not confirmed