Read / write min and max limits „g“ (67h), N 143 – Baumer N 143 User Manual

Page 21

background image

N 143

www.baumer.com

21

4.3.5. Read / write MIN and MAX limits „g“ (67h)

This command reads or writes the MIN and MAX limits within the range from -999.99 to 9999.99. Transmission
is without decimal point.

Example 1: Read limit positions (MIN = 15.00; MAX = 850.25)

SOH Adr Cmd EOT CRC

Transmission

01h 20h 67h 04h 42h

SOH Adr Cmd

MIN limit position = 0015.00

MAX limit position = 0850.25

EOT CRC

Response

01h 20h 67h 30h 30h 31h 35h 30h 30h 30h 38h 35h 30h 32h 35h 04h 1Fh


Example 2: Write limit positions (MIN = -33.22; MAX = 1234.56)

SOH Adr Cmd

MIN limit position = -033.22

MAX limit position = 1234.56

EOT CRC

Transmission

01h 20h 67h 2Dh 30h 33h 33h 32h 32h 31h 32h 33h 34h 35h 36h 04h 92h

Response

SOH Adr Cmd

MIN limit position = -033.22

MAX limit position = 1234.56

EOT CRC

01h 20h 67h 2Dh 30h 33h 33h 32h 32h 31h 32h 33h 34h 35h 36h 04h 92h

4.3.6. Read / write motor speed switching points „h“ (68h)

This command reads or writes the motor speed switching points. Prior to reaching the target the motor speed
can be slowed down to two optional speeds (slow and crawling) for positioning with pinpoint accuracy. The mo-
tor switchoff point can be equally set at an earlier stage prior to attaining the target. The following 2 parameters
are available:

Point of crawling speed:

switching point to slow down from slow to crawling speed.

Point of switchoff:

the SPA will stop the motor here.

The individual switching points are given in relation to the target.

Example 1: Read parameter (crawling speed = 0.70; point for switchoff = 0.00)

SOH Adr Cmd EOT CRC

Transmission

01h 20h 68h 04h 5Ch

SOH Adr Cmd

reserved

crawling speed =0.70

switchoff =0.00

EOT CRC

Response

01h 20h 68h 30h 32h 30h 30h 30h 30h 37h 30h 30h 30h 30h 30h 04h 72h


Example 2: Write parameter (slow speed = 1.25; crawling speed = 0.50; point for switchoff = 0.01)

SOH Adr Cmd

reserved

crawling speed =0,50

switchoff =0.01

EOT CRC

Transmission

01h 20h 68h 30h 31h 32h 35h 30h 30h 35h 30h 30h 30h 30h 31h 04h EAh

SOH Adr Cmd

reserved

crawling speed =0,50

switchoff =0.01

EOT CRC

Response

01h 20h 68h 30h 31h 32h 35h 30h 30h 35h 30h 30h 30h 30h 31h 04h EAh