Technical specifications, Uick, Pecs – Compaq GS60E User Manual
Page 16: Compaq alphaserver gs60e

..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
..
.
Q
UICK
S
PECS
Technical Specifications
16
DA-10352-00A-001
Compaq AlphaServer GS60E
System Unit
Physical Characteristics
Dimensions (HxWxD)
Shipping Dimensions
Weight
Minimum configuration
Maximum configuration
Shipping Weight
Minimum configuration
Maximum configuration
67 x 23.6 x 39.4 in/170 x 60 x 100 cm
76.25 x 36 x 47.9 in/194 x 91.5 x 121.5 cm
650 lbs
775 lbs
750 lbs
875 lbs
Clearances
Operating
Service
Front
Rear
Sides
40 in/1 m
40 in/1 m
0
59 in/1.5 m
40 in/1 m
0
Environmental
Operating
Non-Operating
Temperature
Humidity
Altitude
Vibration
Heat dissipation
41°F to 95°F/5°C to 35°C
10% to 90%
0 to 10,000 ft/0 to 3 km
5 to 500 Hz @ 0.1G maximum
Minimally configured system
1
(system cabinet) 1200W/4100 Btu/hr
Fully configured system
2
(system
cabinet) 2450W / 8300 Btu/hr
Fully configured system
3
(system cabinet with two
I/O expansion cabinets)
5,150W/17,550 Btu/hr
–40°F to 151°F/–40°C to 66°C
10% to 95%
40,000 ft/12,192 m
Regulatory
Agency approvals
UL Listed to UL1950
cUL Listed to CAN/C22.2 No. 950-M89
FCC Part 15 (Class A)
CE Declaration 4206
Reviewed to
EN 60950 1922/A4:1997, European Norm
AS/NZS 3260:1993, Australian/New Zealand Standard
73/23/EEC, Low Voltage Directive
IEC950, second edition, fourth Amendment
Power Requirements
4
US/Canada
Japan
Europe
Nominal voltage
120/208V
202V
380-415V
Frequency range
50 Hz to 60 Hz
50 Hz to 60 Hz
50 Hz to 60 Hz
Phases
3-phase star
3-wire+N+GND
3-phase delta
4-wire mid-GND or
3-wire junction GND
3-phase star
3-wire+N+GND
Maximum input
17A rms
17A rms
9A rms
Surge current
210A peak
210A peak
215A peak
Rating
30A
30A
32A
Power cord length
15 ft/4.5 m
15 ft/4.5 m
15 ft/4.5 m
Power cap (system)
DEC 12-12314-00
DEC 12-12314-01
DEC 12-14379-06
Receptacle (site)
DEC 12-12315-00
DEC 12-12315-01
Hubbell 532R6W
(industry equivalent)
NEMA L21-30R
NEMA L21-30R
IEC 309 (32A)
PCS/PDS/PDU/UPS cable BC24W
BC24W
BN29X
1
Minimally configured system contains three power supplies, dual-CPU module, memory module, system I/O module, CD-ROM,
minimally configured PCI shelf, and one disk drive.
2
Fully configured system contains three power supplies, three dual-CPU modules (six CPUs), two memory modules, two system I/O
modules, two PCI shelves, CD-ROM, and two StorageWorks shelves with 12 disk drives.
3
Fully configured system and two expansion cabinets consist of the above “fully configured system” and two expansion cabinets,
each include three PCI shelves, four StorageWorks shelves, and 24 disk drives.
4
Power system provides near unity power factor which allows full utilization of the input line current (Watts = VA).