Step 2 — Mounting and Electrical Connec-
tions for Motormaster® V Control

48/50P030-060 UNITS — For 48/50P030-035 units, the Mo-

tormaster controlled outdoor-fan motor (OFM) is the no. 1

OFM (see Fig. 3). The no. 2 OFM is controlled by the Com-

fortlink head pressure control routine.

For 48/50P040 units, the Motormaster controlled outdoor-

fan motor (OFM) is the no. 3 OFM (see Fig. 3). The no. 1 and 2

OFMs are controlled by the Comfortlink head pressure control

routine.

For 48/50P050-060 units, the Motormaster controlled out-

door-fan motor (OFM) is the no. 1 OFM (see Fig. 3). The no. 2,

3, and 4 OFMs are controlled by the Comfortlink head pressure

control routine.

Use the following procedure to mount and connect the

MMV controllers to these units:

1. Disconnect power to the unit. Lockout and tag power dis-

connect.

2. Remove control box covers.
3. For size 030-035 units, remove panel from condenser

section on OFM 1 side of the unit in order to gain access

to the outdoor fan section. See Fig. 4. For size 040-060

units, remove panel above control box as shown in Fig. 5

and 6.

4. Mount accessory fuse block HY11UT035 and fan relay

base HN79KK035 inside control box as shown in Fig. 7.

Secure components with ½-in. sheet metal screws.

a. Insert fuses into fuse blocks and relays into relay

bases.

b. Install harness 48EJ402454 from load side of CCB

(control circuit breaker terminals 21, 22, 23) to line

side of MMF (Motormaster V fuse block) as

shown in Fig. 8. Note that it may be easier to pick

up the load side of CCB from the ¼-in. male quick

connect terminals on the line side (terminals 11,

12, 13) of the OFC contactors (see power sche-

matic on control box door).

c. Connect FR (fan relay) coil to OFC1 coil using the

72-in. long 16 gage white and gray wires (stripped

end goes to FR) as shown in Fig. 8.

5. Mount the MMV controller enclosure 30RA500381 on

the bulkhead of the unit inside the outdoor fan section, as

shown in Fig. 4-6, using the mounting brackets

50EJ500656 installed on the enclosure. Remove the en-

closure cover and install the ½-in. HW60EA001 and 1-in.

HW60HH006 connectors in the holes in the lower right

hand side of the enclosure.

6. Connect transducer HK05ZZ001 to the liquid line service

Schrader port of refrigerant Circuit A. Plug transducer ca-

ble 48EJ403240 into transducer. Run cable to the MMV

enclosure, as shown in Fig. 4-6.
Run MMPT (Motormaster V pressure transducer) cable

through ½-in. connector of MMV enclosure (do not tight-

en connector screws at this time). Connect red, green, and

black wires to MMV terminals 6, 5, and 2 as shown in

Fig. 8. Terminate drain wire of transducer cables under

one of the lower MMV mounting screws.

7. Make remaining electrical connections to MMV (see

Fig. 8).

a. In main control box, disconnect black, red, blue,

and green wires from load side (terminals 21, 22,

23) of OFC1 (sizes 030-035, 050-060) contactor or

OFC 3 (size 040) (label cable from OFC1 or OFC3

(size 040) as OFM1 or OFM3 (size 040). Pull

wires out through the hole in the bottom of the

control box and run them up the corner post to the

opening of the cable tray on the side of the control

box, as shown in Fig. 4-6. Run the cable through

the wire tray to the MMV enclosures.

b. Run the OFM1/OFC3 (040) cable through the 1-in.

connector of the MMV enclosure (do not tighten

connector screws at this time). Remove ring termi-

nals from black, red, and blue wires and strip insu-

lation back 3/8-in. Connect black, red, and blue

wires to MMV terminals T1, T2, and T3. Connect

green ground wire to MMV ground screw.

c. In the main control box connect Motormaster VFD

(variable frequency drive) harness 48ZZ401971 to

the load side of the MMF (label the opposite end of

this harness as MMF). Run the harness along the

bottom of the control box and out through the hole

that the OFM harness was in. Pull the harness out

through the hole in the bottom of the control box

and run it through the opening of the cable tray (in

the same manner as the OFM harnesses).

d. Run the MMF cable through 1-in. connector of the

MMV enclosure (do not tighten connector screws

at this time). Connect L1, L2, and L3 wires to

MMV terminals L1, L2, and L3. Connect green

ground wire to MMV ground screw. Place 1 large

varnish cloth 48DA510141 around both cables at

the point they enter the 1-in. connector. Tighten

down connector screws being careful not to dam-

age the cables.

e. In the main control box connect one Motormaster

VFD harness 48ZZ402001 to the NO (normally

open) contact of the FR (see Fig. 8). Run the har-

nesses along the bottom of the control box and out

through the hole that the OFM harness was in. Pull

the harness out through the hole in the bottom of

the control box and run it through the opening of

the cable (in the same manner as the OFM

harness).

WARNING

To avoid possibility of electric shock and personal

injury, open and tag all electrical disconnects before

installing or servicing unit.

WARNING

Hazard of electric shock. Wait three minutes after discon-

necting incoming power before servicing drive. Capacitors

retain charge after power is removed.

CAUTION

To avoid damage to the small terminals on the Motormas-

ter V control, use care when tightening the compression

terminals and use the proper size screwdriver.

CAUTION

DO NOT connect incoming AC power to Motormaster V

output terminals T1, T2, and T3. Severe damage to the con-

trol will result.