beautypg.com

Installation pre-installation, Step 1 — install field-fabricated wind baffles, Warning – Carrier MOTORMASTER 48/50P5030-100 User Manual

Page 3: Caution

background image

3

Table 3 — Motormaster V Control Package Contents — 48/50P070-100 Units

Table 4 — Motormaster V Control Package Usage

INSTALLATION

Pre-Installation —

Inspect the contents of this accessory

package before installing. File a claim with the shipper if there

is shipping damage or if a part is missing.

Step 1 — Install Field-Fabricated Wind Baffles

On size 040-060 units, in areas with prevailing winds of

more than 5 mph (8 kph) and where temperatures drop below

32 F (0° C), wind baffles must be field fabricated to ensure

proper cooling cycle operation at low-ambient temperatures

with Motormaster V controls. Wind baffles are not needed on

size 030, 035, and 070-100 units. See Fig. 2 for baffle details.

Use 20-gage (1 mm) galvanized sheet metal, or similar corro-

sion-resistant material for the baffles. Use field-supplied screws

to attach baffles to unit. Screws should be

1

/

4

-in. (6.3 mm) diam-

eter or larger. Screws should not be more than

1

/

2

-inch in length.

Drill required screw holes for mounting baffles.

ITEM

CRLOWAMB036A00

CRLOWAMB037A00

CRLOWAMB038A00

Connector (

1

/

2

-in.)

HW60EA001 (2)

Connector (1-in.)

HW60HH006 (2)

Controller, 230 V 2 Hp

HR46TN001 (2)

Controller, 460 V 2 Hp

HR46TN002 (2)

Controller, 575 V 2 Hp

HR46TN003 (2)

Enclosure

30RA500381 (2)

Enclosure Cover

30RA500519 (2)

Enclosure Mounting Bracket

50EJ500656 (2)

Fan Relay

HN61KK055 (2)

Relay Base

HN79KK035 (2)

Fuse Block

HY11UT035 (2)

Fuse 15A, KTK-R, Class CC

HY10KB151 (6)

HY10KB151 (6)

Fuse 20A, KTK-R, Class CC

HY10KB200 (6)

Harness Assembly

48ZZ401971 (2)

Harness Assembly

48EJ402454 (2)

Harness Assembly

48ZZ402001 (2)

Label

48ZZ502002

Transducer

HK05ZZ001 (2)

Transducer Harness

48EJ403240 (2)

Varnish Cloth (Large)

48DA510141 (2)

Varnish Cloth (Small)

38C24601 (2)

Wire Tie

HY76TB123 (6)

Wire Tie

HY76TB045 (2)

Wire, 16 Gage 72 in. Long

WHT (2), GRY (2)

UNIT

VOLTAGE

ITEM DESCRIPTION

48/50P030-060

208/230

CRLOWAMB033A00

380, 400, 460

CRLOWAMB034A00

575

CRLOWAMB035A00

48/50P070-100

208/230

CRLOWAMB036A00

380, 400, 460

CRLOWAMB037A00

575

CRLOWAMB038A00

WARNING

To avoid the possibility of electrical shock, open all discon-

nects before installing or servicing this accessory.

CAUTION

To avoid damage to refrigerant coils, electrical compo-

nents, and wiring use extreme care when drilling screw

holes and screwing in fasteners.