Routine No. 2: If DXLOCK (or DX Cooling Lockout is

disabled) < OAT ≤ 68_F when Y1 input is energized, the

economizer will be modulated to maintain SAT at SASP =

SATLO1 + 3_F. If the SAT > SASP + 5_F and the

economizer position > 85% then the economizer will

close the to minimum position for three minutes or until

the SAT > 68_F. The economizer integrator will then be

reset and begin modulating to maintain the SASP after

stage one has been energized for 90 seconds.

When Y2 is energized, the economizer will be modulated

to control to a lower supply air setpoint SASP= SATLO2

+ 3_F If the SAT > SASP + 5_F it will close the

economizer to minimum position for 3 minutes, reset the

integrator for the economizer, then start modulating the

economizer to maintain the SASP after the stage two has

been on for 90 seconds. This provides protection for the

compressor against flooded starts and allow refrigerant

flow to stabilize before modulating the economizer again.

By using return air across the evaporator coil just after the

compressor has started allows for increased refrigerant

flow rates providing better oil return of any oil washed out

during compressor start--up.

Routine No. 3: If the OAT > 68_F and the enthalpy is low

and the OAT < SPT then the economizer will open to

100% and compressors 1 and 2 will be cycled based on

Y1 and Y2 inputs respectively. If any of these conditions

are not met the economizer will go to minimum position.

If there is no call for heating or cooling, the economizer,

if available, will maintain the SASP at 70_F.

Heating — For gas or electric heat, HS1 and HS2 outputs

will follow W1 and W2 inputs respectively. The fan will

also be turned on if it is configured for electric heat.

Heating may also be energized when an IAQ sensor

installed and has overridden the minimum economizer

damper position. If the OAT < 55_F and an IAQ sensor is

installed and the IAQ minimum position > minimum

damper position causing the SAT to decrease below the

SPT -- 10_F, then the heat stages will be cycled to temper

the SAT to maintain a temperature between the SPT and

the SPT + 10_F.

Auxiliary Relay configured for Exhaust Fan — If the

Auxiliary Relay is configured for exhaust fan (AUXOUT

= 1) in the CONFIG configuration table and Continuous

Power Exhaust (MODPE) is enable in the SERVICE

configuration table then the output (HS3) will be

energized whenever the G input is on. If the MODPE is

disabled then output will be energized based on the Power

Exhaust Setpoint (PES) in the SETPOINT table.

Indoor Air Quality — If the optional indoor air quality

(IAQI) sensor is installed, the PremierLink controller will

maintain indoor air quality within the space at the

user--configured differential setpoint (IAQD) in the

CONFIG configuration table. The setpoint is the

difference between the IAQI and an optional outdoor air

quality sensor (OAQ). If the OAQ is not present then a

fixed value of 400 ppm is used. The actual space IAQ

setpoint (IAQS) is calculated as follows:

IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)

As air quality within the space changes, the minimum

position of the economizer damper will be changed also

thus allowing more or less outdoor air into the space

depending on the relationship of the IAQI to the IAQS.

The IAQ algorithm runs every 30 seconds and calculates

IAQ minimum position value using a PID loop on the

IAQI deviation from the IAQS. The IAQ minimum

position is then compared against the user configured

minimum position (MDP) and the greatest value becomes

the final minimum damper position (IQMP). If the

calculated IAQ Minimum Position is greater than the IAQ

maximum damper position (IAQMAXP) decision in the

SERVICE configuration table, then it will be clamped to

IAQMAXP value.

If IAQ is configured for low priority, the positioning of

the economizer damper can be overridden by comfort

requirements. If the SAT < SASP --8_F and both stages of

heat are on for more then 4 minutes or the SAT > SASP +

5_F and both stages of cooling on for more then 4 minutes

then the IAQ minimum damper position will become 0

and the IQMP = MDP. IAQ mode will resume when the

SAT > SASP --8_F in heating or the SAT < SASP + 5_F in

cooling.

If the PremierLink controller is configured for 1 stage of

heat and cool or is only using a single stage thermostat

input, this function will not work as it requires the both

Y1 and Y2 or W1 and W2 inputs to be active. In this

application, it is recommended that the user configure

IAQ priority for high.

If IAQ is configured for high priority and the OAT < 55_F

and the SAT < (SPT --10_F), the algorithm will enable the

heat stages to maintain the SAT between the SPT and the

SPT + 10_F.

CCN SENSOR MODE — When the PremierLink

controller is configured for CCN control, it will control

the compressor, economizer and heating outputs based its

own space temperature input and setpoints or those

received from Linkage. An optional CO

2

IAQ sensor

mounted in the space or received through communications

can also influence the economizer and heating outputs.

The PremierLink controller does not have a hardware

clock so it must have another device on the CCN

communication bus broadcasting time. The controller will

maintain its own time once it has received time as long as

it has power and will send a request for time once a

minute until it receives time when it has lost power and

power is restored. The controller will control to

unoccupied setpoints until it has received a valid time.

The controller must have valid time in order to perform

any broadcast function, follow an occupancy schedule,

perform IAQ pre--occupancy purge and many other

functions as well. The following sections describe the

operation for the functions of the PremierLink controller.