T55/56 Override Duration
This sets the occupancy override duration when the

override button is pushed on the space sensor.

Factory Default = 1 hr

Range = 0--24 hr

IAQ Low Reference @ 4mA
This is used when an IAQ sensor is installed on Input 1 or

2. This value is displayed and used when 4mA is seen at

the input.

Factory Default = 0 PPM

Range = 0--400 PPM

IAQ High Reference @ 20mA
This is used when an IAQ sensor is installed on Input 1 or

2. This value is displayed and used when 20mA is seen at

the input.

Factory Default = 2000 PPM

Range = 0--5000 PPM

NOTE: IAQ low Reference @ 4mA and IAQ High
Reference @ 20mA are used to set the linear curve of mA
vs. PPM.
OAQ Low Reference @ 4mA
This is used when an OAQ sensor is installed on Input 1

or 2. This value is displayed and used when 4mA is seen

at the input.

Factory Default = 0 PPM

Range = 0--400 PPM

OAQ High Reference @ 20mA
This is used when an OAQ sensor is installed on Input 1

or 2. This value is displayed and used when 20mA is seen

at the input.

Factory Default = 2000 PPM

Range = 0--5000 PPM

NOTE: OAQ low Reference @ 4mA and OAQ High
Reference @ 20mA are used to set the linear curve of mA
vs. PPM.
Economizer
Economizer Exists
This point tells the controller if there is an economizer

installed on the unit.

Factory Default = NO if no economizer

YES if there is an economizer installed

Economizer Minimum Position
This defines the lowest economizer position when the

indoor fan is running and the building is occupied.

Factory Default = 20%

Range = 0--100 %

Economizer High OAT Lockout
If the outdoor air temperature rises above this value,

economizer cooling will be disabled and dampers will

return and stay at minimum position.

Factory Default = 75_F

Range = 55--80_F

Power Exhaust Setpt
When the economizer damper position opens above this

point the power exhaust operation will begin. When the

damper position falls 10% below the setpoint, the power

exhaust will shutdown.

Factory Default = 50%

Range = 20--90 %

NOTE: This point is only used when Continuous Occ
Exhaust = NO
Continuous Occ Exhaust
This point tells the controller when to run the power

exhaust if equipped on the unit. If set to YES, the power

exhaust will be on all the time when in occupied mode

and will be off when in unoccupied mode. If set to NO the

power exhaust will be controlled by the Power Exhaust

Setpoint.

Factory Default = NO

IAQ
Max Differential CO

2

Setpt

If the difference between indoor an outdoor air quality

becomes greater then this value the damper position will

stay at the IAQ Greatest Min Dmpr Pos. configuration

point

Factory Default = 650 PPM

Range = 300--950 PPM

IAQ Greatest Min Dmpr Pos.
This is the greatest minimum position the economizer will

open to while trying to control the indoor air quality, CO

2

differential.

Factory Default = 50% open

Range = 10--60% open

Clockset
This submenu screen allows you to set the date and time

manually. The Daylight Savings Time (DST) can also be

changed here. The date and time is automatically set when

ever software is downloaded. The clock is a 24 hour clock

and not am/pm. The time should be verified (and maybe

changed) according to unit location and time zone.

Factory Default = Eastern Standard Time

USERPW
This submenu screen allows you to change the user

password to a four number password of choice. The User

password change screen is only accessible with the

Administrator Password (1111). The ADMIN password

will always override the user password.