Cooling/Econ SAT Low Setpt
The supply air temperature must remain above this value

to allow cooling with the economizer and/or compressors.

There is 5_F plus and minus deadband to this point. If the

SAT falls below this value during cooling, all compressors

will be staged off. The economizer will start to ramp

down to minimum position when the SAT = this

configuration +5_F.

Factory Default = 50_F

Range = 45--75_F

Cooling Lockout Temp
This defines the minimum outdoor air temperature that

cooling mode can be enabled and run. If the OAT falls

below this threshold during cooling, then compressor

cooling will not be allowed.

Factory Default = 45_F

Range = 0--65_F

Heating
Heating SAT High Setpt
The supply air temperature must remain below this value

to allow heating. There is 5_F plus and minus deadband to

this point. If the SAT rises above this value during heating

the heat stages will begin to decrease until the SAT has

dropped below this value.

Factory Default = 120_F

Range = 95--150_F

Heating Lockout Temp
This defines the maximum outdoor air temperature that

heating mode can be enabled and run. If the OAT rises

above this threshold during heating, then heating will not

be allowed.

Factory Default = 65_F

Range = 49--95_F

Inputs
NOTE
:

For installation of inputs and field installed

accessories, refer to the appropriate sections.
Input 3
This input is a discrete input and can be configured to be

one of five different inputs: No Function, Compressor

Safety, Fan Status, Filter Status, or Remote Occupancy.

This input can also be configured to be either Normally

Open (N/O) or Normally Closed (N/C). Input 3 is factory

wired to pin J1--2. Field accessories get wired to its

parallel pin J5--5. Do not connect inputs to both locations,

one function per input.

Factory Default = Compressor Safety and N/O

NOTE: Compressor Safety input comes from the CLO
board. J1--2 is always factory wired to TB1--8 (X) terminal
on the unit. If the unit has a CLO board, do not configure
input 3 for anything but Compressor Safety.

Input 5
This input is a discrete input and can be configured to be

one of five different inputs: No Function, Fire Shutdown,

Fan Status, Filter Status, or Remote Occupancy. This

input can also be configured to be either Normally Open

(N/O) or Normally Closed (N/C). Input 5 is factory wired

to pin J1--10. Field accessories get wired to its parallel pin

J5--3. Do not connect inputs to both locations, one

function per input.

Factory Default = Fire Shutdown and N/C

NOTE: Fire Shutdown input comes from TB4--7. J1--10
is always factory wired to TB4--7. Only change input 5s
function if absolutely needed.
Input 8
This input is a discrete input and can be configured to be

one of five different inputs: No Function, Enthalpy

Switch, Fan Status, Filter Status, or Remote Occupancy.

This input can also be configured to be either Normally

Open (N/O) or Normally Closed (N/C). Input 8 is factory

wired to pin J2--6. Field accessories get wired to its

parallel pin J5--1. Do not connect inputs to both locations,

one function per input.

Factory Default = No Function and N/O

Input 9
This input is a discrete input and can be configured to be

one of five different inputs: No Function, Humidistat, Fan

Status, Filter Status, or Remote Occupancy. This input can

also be configured to be either Normally Open (N/O) or

Normally Closed (N/C). Input 9 is factory and field wired

to pin J5--7. Do not connect inputs to both locations, one

function per input.

Factory Default = Humidistat and N/O

Space Sensor Type
This tells the controller what type of space sensor is

installed to run the unit. The three types that can be used

are the T55 space sensor, the T56 space sensor, or the RS

space sensor.

Factory Default = T55 Type

Input 1 Function
This input is an analog input and can be configured to be

one of five different inputs: No Sensor, IAQ Sensor, OAQ

Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1

is wired to pin J4--5.

Factory Default = No Sensor

Input 2 Function
This input is an analog input and can be configured to be

one of five different inputs: No Sensor, IAQ Sensor, OAQ

Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2

is wired to pin J4--2.

Factory Default = No Sensor

Setpoint Slider Range
This sets the slider range of the space sensor (with this

built in function). The slider is used to offset the current

control setpoint.

Factory Default = 5 n_F
Range = 0--15 n_F

48TC