beautypg.com

Exide Technologies Section 92.61 User Manual

Page 22

background image

- 18 -

C. Proceed to Step 3.

STEP 3

The initial charge is complete. Charger voltage can now be

reduced to float voltage setting per Section 12.2. For a target

float charge of 2.25 VPC on a 24-cell system, you would set

the charger voltage to 54 volts.

SECTION 12

12.0 Operation

12.0.1 Cycle Method of Operation

In cycle operation, the degree of discharge will vary for dif-

ferent applications. Therefore, the frequency of recharging

and the amount of charge necessary will vary. The amount

of charge necessary depends on the number of ampere

hours discharged. Generally, Absolyte GP cells require

approximately 105-110% of the ampere-hours removed to be

returned to achieve a full state of charge.

The upper voltage settings recommended, given that the

maxium charge current is 5% of the nominal C

100

Amp-hour

rating and ambient temperatures of 25°C (77°F), are as fol-

lows:

2.28 ± 0.02 VPC @ 0-2% DOD

2.33 ± 0.02 VPC @ 3-5% DOD

2.38 ± 0.02 VPC @ >5% DOD

Due to the variety of applications and charging equipment

(particularly in Photovoltaic systems) it is recommended that

you contact an GNB representative when determining proper

recharge profiles.

12.1 Floating Charge Method

In this type of operation, the battery is connected in parallel

with a constant voltage charger and the critical load circuits.

The charger should be capable of maintaining the required

constant voltage at battery terminals and also supply a nor-

mal connected load where applicable. This sustains the bat-

tery in a fully charged condition and also makes it available

to assume the emergency power requirements in the event of

an AC power interruption or charger failure.

12.2

Float Charge - Float Voltages

Following are the float voltage ranges recommended for the

Absolyte Battery System. Select any “volts per cell” (VPC)

value within the range listed that will result in the series string

having an average volts per cell equal to that value.

RECOMMENDED FLOAT RANGE (@77°F)

2.23 to 2.27 VPC

NOTE: Recommended float voltages are for 77°F. For other

temperatures a compensation factor of .003 V/°F (.0055 V/°C)

per cell is recommended. The minimum voltage is 2.20 VPC,

temperature correction does not apply below this voltage. The

maximum voltage is 2.35 VPC, temperature correction does not

apply above this voltage.

TEMPERATURE CORRECTION

V corrected = V25°C - (( T actual-25°C) x ( .0055V/°C)) or

V corrected = V77°F - ((T actual-77°F) x (.003V/°F))

See Appendix A for standard values.

Modern constant voltage output charging equipment is recom-

mended for the floating charger method of operation of GNB

Absolyte batteries. This type of charger, properly adjusted to the

recommended float voltages and following recommended surveil-

lance procedures, will assist in obtaining consistent serviceability

and optimum life.

After the battery has been given its initial charge (refer to

Section 11), the charger should be adjusted to provide the

recommended float voltages at the battery terminals.

Do not use float voltages higher or lower than those recom-

mended. Reduced capacity or battery life will result.

Check and record battery terminal voltage on a regular

basis. Monthly checks are recommended. See Section 15.0,

Records, second bullet. If battery float voltage is above or

below the correct value, adjust charger to provide proper volt-

age as measured at the battery terminals.

12.3

Voltmeter Calibration

Panel and portable voltmeters used to indicate battery float

voltages should be accurate at the operating voltage value.

The same holds true for portable meters used to read indi-

vidual cell voltages. These meters should be checked against

a standard every six months and calibrated when necessary.

12.4 Recharge

All batteries should be recharged as soon as possible follow-

ing a discharge with constant voltage chargers. However, to

recharge in the shortest period of time, raise the charger out-

put voltage to the highest value which the connected system

will permit. Do not exceed the voltages and times listed in

Table C, Section 13.2.

12.5

Determining State-of-Charge

If the normal connected load is constant (no emergency load

connected), the following method can be used to determine

the approximate state-of-charge of the battery. The state-of-

charge can be identified to some degree by the amount of

charging current going to the battery. When initially placed

on charge or recharge following a discharge, the charging

current, read at the charger ammeter, will be a combination

of the load current plus the current necessary to charge the

battery. The current to the battery will start to decrease and

will finally stabilize when the battery becomes fully charged.

If the current level remains constant for three consecutive

hours, then this reflects a state-of-charge of approximately 95

to 98%. For most requirements, the battery is ready for use.

If the normal connected load is variable (i.e. telecommunica-

tions), the following method may be used to check the state-

of-charge of the battery. Measure the voltage across a pilot

cell (See Section 14.0 for definition of pilot cell). If the voltage

is stable for 24 consecutive hours, the battery reflects a state

of charge of approximately 95%.