H. Proceed with stacking of remaining modules, checking

that stack is plumb in both axes as stacking progresses

before torquing hardware. Be certain to check the

layout/wiring diagram for correct horizontal orientation to

provide proper polarity interconnection as stacking

progresses. See Figure 17B.

8.2

Horizontal-Multiple Stacks

It is recommended that all of the first modules with bottom

supports attached (see Section 8.1.1) be placed in position

first. A chalk line floor mark should be used to assure all

stacks will be in a straight line. This applies for stacks end-

to-end or end-to-end and back-to-back. Also refer to Section

8.1.3, Items A through H (Item E for base module leveling).
Module ends should be butted together so that module side

channel ends meet (see Figure 18).
Refer to layout/wiring diagram for seismic shim requirements.
At this time stack tie plates should be installed (see Section

8.2.1). It will be necessary to temporarily remove the hard-

ware fastening the base modules to the I-beams.
See Figure 20A. Install tie plates and hardware. Torque to 47

Newton-meters (35 Ft-Lbs).
For stacks back-to-back, the two base modules are posi-

tioned to provide a minimum 4.5” spacing between the bot-

toms of the modules (not I-beam edges). See Figure 19A.
When all base modules are set in place, continue with stack-

ing of subsequent modules. Procedures for assembly of

multiple horizontal stacks are the same as outlined in section

9.1. Also consult layout/wiring diagram. Each stack should be

built up in sequence to the same level until the top modules

in all stacks are the last to be installed. The use of a line cord

attached to upper module corners of opposite end modules

as stacking progresses aids in alignment. See Figure 19B.

- 10 -

INSTALLING HARDWARE

Figure 17A

COMPLETED HORIZONTAL STACK

Figure 17B

HANDLING AND STACKING HORIZONTAL MODULES

Figure 15

HARDWARE INSTALLATION SEQUENCE

Figure 16

POSITIONING HORIZONTAL BASE MODULE

Figure 18

M10 SERRATED

FLANGE BOLT

M10 SERRATED

FLANGE NUT