1.2.3 Wiring Requirements
Wiring requirements are summarized in the following table. As wires are pulled
through conduit, ensure there is at least 6 ft. of wire extending from the end of the
conduit stub. The Network (CAT-5) cable will need to be terminated with 8 position
RJ-45 connectors per Ethernet standard 568B.
Circuit Description
Wire Qty
Wire Description
Power (115-120 VAC, 8 Amps).
3
16 AWG (black/white/green)
Network connection (to router)
1
Cat 5 communications cable, 295 ft max length
Wash Control
Varies
Per wash equipment manufacturer’s instructions
Intercom (Optional)
2-4
22 AWG minimum, Qty varies by intercom model