3.3 Temperature Monitoring
To avoid overheating of the system, the controller and motor temperatures are monitored. If the
controller temperature exceeds 70°C (158°F) or the motor temperature 90°C (194°F) for longer than 10
minutes, the system goes into an error state and the pump stops. At 80°C (176 F) controller
temperature or 100°C (212°F) motor temperature, the system immediately stops.