beautypg.com

Settings, Step five, Power on – tekmar 650 Snow Melting Control User Manual

Page 3: Viewing, Programming, Initiating operating mode

background image

3 of 4

© 2010 D 650 - 08/10

Step Five

Troubleshooting

First observe the system operating parameters. The source of the problem can often be identified by noting a temperature or time
reading which seems unreasonable. Observing what the control is doing, and understanding the sequence of operation greatly aids
in troubleshooting. If there is a sensor fault, the control displays an error message. Use the error message table provided below to
determine which circuit has the fault and then refer to Step Four for testing of the wiring and sensors.

Settings

Outdoor temperature - the temperature measured by the Outdoor Sensor.

Slab Sensor temperature - the temperature measured by the Slab Sensor. This sensor should be 1” below the slab surface.

Target Slab temperature - the control calculates a “Target Slab” temperature to maintain the slab surface at the “Melting” or “Idling”
setting when the Slab Sensor is placed 1” below the slab surface and halfway between the pipes or electric cables (See Step Three
of this brochure). The “Target Slab” temperature is calculated from the “Melting” or “Idling” setting and the measured “Outdoor”
temperature. As the “Outdoor” temperature drops or the “Melting” or “Idling” setting is raised, the “Target Slab” temperature increases.

On Time - when the control is in melting mode, the On Time display indicates the time left until the control exits melting mode. When
programming, the On Time can be set from 30 minutes to 19 hours 50 minutes or it can be set to “Inf” (Infinite). When the On Time
is set to “Inf”, the control remains in melting mode indefinitely until the “STOP” button is pressed.

Melting temperature - the “Melting” temperature is the desired slab surface temperature when the control is in melting mode and is
also used as the Warm Weather Cut Off temperature. The slab “Melting” temperature is usually set based on the local weather
conditions. In some areas, heavy snowfall can load a slab at temperatures well above freezing; in these areas, the “Melting”
temperature is set higher. In general if the melting system response is sluggish, increasing the “Melting” temperature causes the
system to melt faster. It is important to remember that increasing this setting increases the snow melt system energy consumption.

Idling temperature - the “Idling” temperature is set based on the requirements of the user. To minimize the time required for the slab
to reach “Melting” temperature, “Idling” is set slightly below freezing (<32°F). To prevent black ice or frost formation, “Idling” is set
slightly above freezing (>32°F). It is important to remember that idling increases energy consumption. Idling can also be set to “Off”.

Cold Weather Cut Off (CWCO) - the “CWCO” temperature is the lowest outdoor temperature at which the melt system operates. This
setting is based on the economics of melting in extreme conditions and the melting capabilities of the snow melt system.

On

Time

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

Outdoor Sensor Open/Short Circuit
The display flashes “Err” and the
“Outdoor” pointer. The control con-
tinues operation assuming an out-
door temperature of 20°F (-7°C).

On

Time

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

Slab Sensor Open/Short Circuit
The display flashes “Err” and the
“Slab Sensor” pointer. The control
shuts down the melting system with
this error.

Press and Release the

“Item” button to change the

display from the “Outdoor”

temperature to the “Slab

Sensor” temperature.

Use the arrow keys to program

the “Melting” temperature.

Note: The control automatically exits out of programming when the buttons are left alone for 20 seconds

Note: The control automatically exits out of programming when the buttons are left alone for 20 seconds

When the control is

powered-up, all display

elements are turned on.

POWER ON

After approximately three

seconds, the “Outdoor”

temperature is displayed.

VIEWING

Press and Release the

"Item" button to change the

display to the "Target Slab"

temperature.

Press and Release the

"Item" button to change the

display to the "On Time"

remaining.

PROGRAMMING

When no Idling function is

desired, set Idling to “OFF”.

Use the arrow keys to program

the “Idling” temperature.

Use the arrow keys to set

the “CWCO” temperature.

When no CWCO is desired,

set CWCO to “OFF”.

Use the arrow keys to switch

between “°F” and “°C”.

Use the arrow keys to program the

“On Time" in hours and minutes.

If the control is not in

melting or idling mode, no

"Target Slab" temperature is

displayed.

If the control is not in

melting mode no “On

Time” is displayed.

Continue to

Press and

Release the “Item” button.

The word “PRGM” is

displayed and the “On

Time” pointer flashes.

On

Time

F

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

Press and Release the

“Item” button to change the

display to the “Melting”

temperature.

Press and Release the

“Item” button to change

the display to the “Idling”

temperature.

Press and Release the

“Item” button to change the

display to “°F” or “°C”.

On

Time

Outdoor

Slab Sensor

Target Slab

Melting

PRGM

CWCO

Idling

On

Time

F

Outdoor

Slab Sensor

CWCO

Idling

Target Slab

Melting

On

Time

Outdoor

Slab Sensor

CWCO

Idling

Target Slab

Melting

On

Time

PRGM

F

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

On

Time

F

Outdoor

Target Slab

CWCO

Idling

Slab Sensor

Melting

PRGM

On

Time

F

Outdoor

Target Slab

CWCO

Slab Sensor

Melting

Idling

PRGM

On

Time

F

Outdoor

Target Slab

Idling

Slab Sensor

Melting

PRGM

If the DIP

switch is set to

“Melt at power

up”, the control

switches into

“Melting” mode

when it is

powered up.

If the control is

already powered up

and you are not

programming,

Press and Release

the "Start" button.

When the control is in

melting mode the

melting pointer

flashes.

INITIATING

OPERATING MODE

When the control is not in CWCO or WWCO, the

melt system is turned on as follows:

OR

On

Time

F

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

On

Time

F

Outdoor

Target Slab

CWCO

Idling

Slab Sensor

Melting

Press and Release the

“Item” button to change the

display to the “CWCO”

temperature.

On

Time

Outdoor

Slab Sensor

Target Slab

Melting

PRGM

CWCO

Idling

On

Time

F

Outdoor

Target Slab

CWCO

Idling

Slab Sensor

Melting

PRGM

CWCO

Melt at power up

On
Off

Item

Start

Stop

On

Time

Outdoor

Slab Sensor

CWCO

Idling

Target Slab

Melting

On

Time

F

Slab Sensor

Target Slab

CWCO

Idling

Melting

Outdoor

On

Time

PRGM

F C

Outdoor

Slab Sensor

Target Slab

CWCO

Idling

Melting

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop

Item

Start

Stop