beautypg.com

tekmar 529 Thermostat Installation User Manual

Page 25

background image

25 of 28

© 2011

D 529 - 12/11

Symptom

Look for...

Corrective Action

No Heat

H1 Symbol

H1 symbol indicates heat is on. Check if

zone valve or zone pump is operating.

Flashing

WWSD

Increase WWSD setting on tekmarNet

®

reset control.

Flashing Away

Change User Switch to Normal scene 1.

Heat on before

scheduled time

Optimum start “learns” the heat up and

cool off rate of the room and starts the

heating or cooling early so that the room is

comfortable at the scheduled time.

Pressing

button does
not increase
temperature

Flashing Max

Installer can increase the Maximum Set
Room Heat.

Flashing Floor

Max

Floor temperature has reached the Floor
Maximum setting. If the floor is not heated,
then the floor sensor may be faulty and
require replacement.

Pressing

button does
not decrease
temperature

Flashing Min

Installer can decrease the Minimum Set
Room Heat.

Floor Min

Floor minimum takes priority over the air
heating temperature. Recommend turning
down the floor minimum temperature
setting.

Frequently Asked Questions