tekmar 511 Programmable Thermostat Installation User Manual
Page 12

© 2012
D 510 - 02/12
12 of 16
ROOM HEAT UnOcc
Desired temperature for heating during UnOccupied.
(Must have an active air sensor and be set to Heat.)
35 to 100°F (1.5 to 38.0°C)
Adjust Menu (2 of 3)
ROOM HEAT Occ
Desired temperature for heating during Occupied.
(Must have an active air sensor and be set to Heat.)
35 to 100°F (1.5 to 38.0°C)
ROOM HEAT Sleep
Desired temperature for heating during Sleep.
(Must have an active air sensor and be set to Heat.)
35 to 100°F (1.5 to 38.0°C)
SLAB MINIMUM Wake
Minimum slab temperature during Wake.
(Must have an active slab sensor.)
OFF, 34 to 122°F (OFF, 1.0 to 50.0°C)
SLAB MINIMUM UnOcc
Minimum slab temperature during UnOccupied.
(Must have an active slab sensor.)
OFF, 34 to 122°F (OFF, 1.0 to 50.0°C)
SLAB MINIMUM Occ
Minimum slab temperature during Occupied.
(Must have an active slab sensor.)
OFF, 34 to 122°F (OFF, 1.0 to 50.0°C)
SLAB MINIMUM Sleep
Minimum slab temperature during Sleep. (Must have an active
slab sensor.)
OFF, 34 to 122°F (OFF, 1.0 to 50.0°C)
SLAB MAXIMUM
Maximum slab temperature. This item is only available in the
Installer access level. (Must have an active slab sensor.)
34 to 122°F, OFF (1.0 to 50.0°C, OFF)