Adjust Menu

Item

Description

MODE

Select one of the following modes to operate the heat pump and backup.

AUTO - Automatic switchover between heating and cooling.
COOL - Heat pump only operates to satisfy cooling calls. A backup boiler satisfies DHW or Setpoint calls.
HEAT - Heat pump only operates to satisfy heating calls. A backup boiler satisfies any DHW,
Setpoint, or Boil calls, and provides backup to Tank and Mix calls.
BKUP - The heat pump is disabled and the backup boiler satisfies any DHW, Setpoint, Tank, Mix
or Boil calls.
OFF - Both the heat pump and backup are disabled.



WWSD

Warm Weather Shut Down is the outdoor temperature at which the control will no longer turn on the
heat pump or backup for space heating.

40 to 100°F (4.5 to 38°C)

UNITS

Selects units for temperature display.

°F or °C

The Adjust menu items are the programmable settings used to determine how to operate the system.

Item

Description

MIXING

Current mix supply water temperature as measured by the mix sensor.
Note: This item is only available when a mix water temperature is selected.

MIX TARGET

The temperature the control is currently trying to maintain at the mix sensor. “– – –” is displayed when
no heat is required for mix zones.
Note: This item is only available when a mix water temperature is selected.

TANK

Current tank supply water temperature as measured by the tank sensor.

TANK TARGET

The temperature the control is currently trying to maintain at the tank sensor. “– – –” is displayed when no
heat is required for tank zones.

DOMESTIC HOT WATER

Current Domestic Hot Water tank temperature as measured by the optional DHW sensor.
Note: This item is only available when a DHW sensor is installed.

HEAT PUMP

Current heat pump return water temperature as measured by the HP Return sensor.