beautypg.com

Bryant Deluxe 4-Way Multipoise Variable-Capacity Direct-Vent Condensing Gas 355MAV User Manual

Page 8

background image

G.

Upper Collector Box and Inducer Housing (Unused)

Drain Connections

UPPER COLLECTOR BOX DRAIN CONNECTION

Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white striped
label). This tube is plugged to prevent condensate leakage in this
application. Ensure this tube is plugged.

NOTE:

See Fig. 7 or 8 or tube routing label on main furnace door

to check for proper connections.

UPPER INDUCER HOUSING DRAIN CONNECTION

Attached to the UPPER (unused) inducer housing drain connection
is a cap and clamp. This cap is used to prevent condensate leakage
in this application. Ensure this connection is capped.

NOTE:

See Fig. 7 or 8 or tube routing label on main furnace door

to check for proper connections.

H.

Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda-
tions and procedures.

III.

DOWNFLOW APPLICATIONS

A downflow furnace application is where furnace blower is located
above combustion and controls section of furnace, and conditioned
air is discharged downwards.

A.

Condensate Trap Location

The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application location
as shown in Fig. 2, 9, or 10.

To relocate condensate trap from the blower shelf to desired
location, perform the following:

1. Remove 3 tubes connected to condensate trap.

2. Remove trap from blower shelf by gently pushing tabs

inward and rotating trap.

3. Remove casing hole filler cap from casing hole. (See Fig. 2

and 10.)

4. Install casing hole filler cap (factory-supplied in loose parts

bag) into blower shelf hole where trap was removed.

WARNING:

Casing hole filler cap must be installed in

blower shelf hole when condensate trap is relocated.
Failure to follow this warning could result in electrical
shock, fire, personal injury or death.

5. Install condensate trap into left-hand side casing hole by

inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.

6. Fill unused condenstate trap casing holes with plastic filler

caps (factory-supplied in loose parts bag).

B.

Condensate Trap Tubing

NOTE:

See Fig. 9 or 10 or tube routing label on main furnace

door to check for proper connections.

1. Collector Box Drain Tube

a. Remove factory-installed plug from LOWER collector

box drain tube (blue and white striped label).

b. Install removed clamp and plug into UPPER collector

box drain tube (blue label) which was connected to
condensate trap.

c. Connect LOWER collector box drain connection to

condensate trap.

(1.) Condensate Trap Located on Left Side of Casing

(a.) Connect LOWER collector box drain tube

(blue and white striped label) to condensate
trap. Tube does not need to be cut.

(b.) Clamp tube to prevent any condensate leakage.

Fig. 9—Downflow Tube Configuration

(Left-Hand Trap Installation)

A94215

PLUG

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

DRAIN TUBE (BLUE

& WHITE STRIPED)

COLLECTOR BOX

EXTENSION TUBE

CONDENSATE

TRAP

INDUCER HOUSING

DRAIN TUBE (VIOLET)

CAP

COLLECTOR BOX

DRAIN TUBE (BLUE)

Fig. 10—Downflow Tube Configuration

(Right-Hand Trap Installation)

A94216

PLUG

COLLECTOR BOX
TUBE (GREEN)

COLLECTOR BOX
TUBE (PINK)

COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)

COLLECTOR BOX
EXTENSION
DRAIN TUBE

CONDENSATE
TRAP

INDUCER HOUSING
DRAIN TUBE
(VIOLET)

COLLECTOR BOX
EXTENSION TUBE

DRAIN TUBE
COUPLING

COLLECTOR BOX
DRAIN TUBE (BLUE)

CAP

—8—