Commercial gas burner oem setup guide, H. b. smith he28 – Beckett CG25 User Manual
Page 7

Commercial Gas Burner OEM Setup Guide
Boiler
Burner
Firing Mode
Rate
MBH
Manifold
Pressure
in. water
Damper
Setting
Blue / Red
Head Type
/ Head
Setting
Shutter
Band
Settings
Air Tube
Insertion
Inches
H. B. Smith HE28
HE28- 4
CG15
Mod
580 / 1146
1.15 / 4.55
15.2S / 15.2
25 / 58
-
4.875"
HE28- 5
CG25
Mod
730 / 1467
0.65 / 2.9
25.2S / 25.2
21 / 42
-
4.875"
HE28- 6
CG25
Mod
899 / 1794
0.75 / 3.15
25.3S / 25.3
25 / 50
-
4.875"
HE28- 7
CG25
Mod
1048 / 2097
0.8 / 3.35
25.4S / 25.4
28 / 60
-
4.875"
HE28- 7
CG50
Low/High
1058 / 2103
0.8 / 3.2
50.1S / 50.1
19 / 34
-
4.875"
HE28- 7
CG50
Mod
889 / 2103
0.55 / 3.2
50.1S / 50.1
17 / 34
-
4.875"
HE28- 8
CG25
Mod
1221 / 2411
0.8 / 3.25
25.5S /25.5
32 / 105
-
4.875"
HE28- 8
CG50
Mod
1047 / 2435
0.55 / 3.1
50.2S / 50.2
20 / 38
-
4.875"
HE28- 9
CG50
Mod
1053 / 2724
0.55 / 3.8
50.2S / 50.2
21 / 43
-
4.875"
HE28- 9
CG50
Low/High
1367 / 2724
0.85 / 3.8
50.2S / 50.2
23 / 43
-
4.875"
HE28-10
CG50
Mod
1241 / 3081
0.55 / 3.5
50.3S / 50.3
21 / 50
-
4.875"
HE28-10
CG50
Low/High
1520 / 3081
0.8 / 3.5
50.3S / 50.3
25 / 50
-
4.875"
HE28-11
CG50
Mod
1463 / 3396
0.55 / 3.2
50.4S / 50.4
23 / 50
-
4.875"
HE28-11
CG50
Low/High
1676 / 3396
0.8 / 3.2
50.4S / 50.4
26 / 50
-
4.875"
HE28-12
CG50
Mod
1449 / 3679
0.55 / 3.7
50.4S / 50.4
26 / 60
-
4.875"
HE28-12
CG50
Low/High
1849 / 3679
0.85 / 3.7
50.4S / 50.4
30 / 60
-
4.875"
HE28-13
CG50
Mod
1711 / 3982
0.55 / 3.2
50.5S / 50.5
26 / 70
-
4.875"
HE28-13
CG50
Low/High
2009 / 3982
0.8 / 3.2
50.5S / 50.5
30 / 70
-
4.875"
HE28-14
CG50
Mod
1709 / 4299
0.55 / 3.7
50.5S / 50.5
26 / 90
-
4.875"
HE28-14
CG50
Low/High
2149 / 4299
0.85 / 3.7
50.5S / 50.5
31 / 90
-
4.875"