beautypg.com

Commercial gas burner oem setup guide, H. b. smith he28 – Beckett CG25 User Manual

Page 7

background image

Commercial Gas Burner OEM Setup Guide

Boiler

Burner

Firing Mode

Rate

MBH

Manifold

Pressure

in. water

Damper

Setting

Blue / Red

Head Type

/ Head

Setting

Shutter

Band

Settings

Air Tube

Insertion

Inches

H. B. Smith HE28

HE28- 4

CG15

Mod

580 / 1146

1.15 / 4.55

15.2S / 15.2

25 / 58

-

4.875"

HE28- 5

CG25

Mod

730 / 1467

0.65 / 2.9

25.2S / 25.2

21 / 42

-

4.875"

HE28- 6

CG25

Mod

899 / 1794

0.75 / 3.15

25.3S / 25.3

25 / 50

-

4.875"

HE28- 7

CG25

Mod

1048 / 2097

0.8 / 3.35

25.4S / 25.4

28 / 60

-

4.875"

HE28- 7

CG50

Low/High

1058 / 2103

0.8 / 3.2

50.1S / 50.1

19 / 34

-

4.875"

HE28- 7

CG50

Mod

889 / 2103

0.55 / 3.2

50.1S / 50.1

17 / 34

-

4.875"

HE28- 8

CG25

Mod

1221 / 2411

0.8 / 3.25

25.5S /25.5

32 / 105

-

4.875"

HE28- 8

CG50

Mod

1047 / 2435

0.55 / 3.1

50.2S / 50.2

20 / 38

-

4.875"

HE28- 9

CG50

Mod

1053 / 2724

0.55 / 3.8

50.2S / 50.2

21 / 43

-

4.875"

HE28- 9

CG50

Low/High

1367 / 2724

0.85 / 3.8

50.2S / 50.2

23 / 43

-

4.875"

HE28-10

CG50

Mod

1241 / 3081

0.55 / 3.5

50.3S / 50.3

21 / 50

-

4.875"

HE28-10

CG50

Low/High

1520 / 3081

0.8 / 3.5

50.3S / 50.3

25 / 50

-

4.875"

HE28-11

CG50

Mod

1463 / 3396

0.55 / 3.2

50.4S / 50.4

23 / 50

-

4.875"

HE28-11

CG50

Low/High

1676 / 3396

0.8 / 3.2

50.4S / 50.4

26 / 50

-

4.875"

HE28-12

CG50

Mod

1449 / 3679

0.55 / 3.7

50.4S / 50.4

26 / 60

-

4.875"

HE28-12

CG50

Low/High

1849 / 3679

0.85 / 3.7

50.4S / 50.4

30 / 60

-

4.875"

HE28-13

CG50

Mod

1711 / 3982

0.55 / 3.2

50.5S / 50.5

26 / 70

-

4.875"

HE28-13

CG50

Low/High

2009 / 3982

0.8 / 3.2

50.5S / 50.5

30 / 70

-

4.875"

HE28-14

CG50

Mod

1709 / 4299

0.55 / 3.7

50.5S / 50.5

26 / 90

-

4.875"

HE28-14

CG50

Low/High

2149 / 4299

0.85 / 3.7

50.5S / 50.5

31 / 90

-

4.875"

This manual is related to the following products: