Commercial gas burner oem setup guide, Armstrong lg-14 – Beckett CG25 User Manual
Page 2

Commercial Gas Burner OEM Setup Guide
Boiler
Burner
Firing Mode
Rate
MBH
Manifold
Pressure
in. water
Damper
Setting
Blue / Red
Head Type
/ Head
Setting
Shutter
Band
Settings
Air Tube
Insertion
Inches
Armstrong LG-14
280 LP
CG10
On/Off
282
1.9
10.1S / 10.1
-
1.5 / 0
2.25"
280 Nat
CG10
On/Off
284
2.2
10.1S / 10.1
-
1.5 / 0
2.25"
350 LP
CG10
On/Off
350
2.9
10.1S / 10.1
-
2.5 / 0
2.25"
350 Nat
CG10
On/Off
351
3.4
10.1S / 10.1
-
3 / 0
2.25"
420 LP
CG10
On/Off
422
1.3
10.3S / 10.3
-
4 / 0
2.25"
420 Nat
CG10
On/Off
419
1.2
10.3S / 10.3
-
3.5 / 0
2.25"
500 LP
CG10
On/Off
498
1.8
10.3S / 10.3
-
6.5 / 0
2.25"
500 Nat
CG10
On/Off
499
1.7
10.3S / 10.3
-
5.5 / 0
2.25"