Commercial Gas Burner OEM Setup Guide

Boiler

Burner

Firing Mode

Rate

MBH

Manifold

Pressure

in. water

Damper

Setting

Blue / Red

Head Type

/ Head

Setting

Shutter

Band

Settings

Air Tube

Insertion

Inches

Armstrong LG-14

280 LP

CG10

On/Off

282

1.9

10.1S / 10.1

-

1.5 / 0

2.25"

280 Nat

CG10

On/Off

284

2.2

10.1S / 10.1

-

1.5 / 0

2.25"

350 LP

CG10

On/Off

350

2.9

10.1S / 10.1

-

2.5 / 0

2.25"

350 Nat

CG10

On/Off

351

3.4

10.1S / 10.1

-

3 / 0

2.25"

420 LP

CG10

On/Off

422

1.3

10.3S / 10.3

-

4 / 0

2.25"

420 Nat

CG10

On/Off

419

1.2

10.3S / 10.3

-

3.5 / 0

2.25"

500 LP

CG10

On/Off

498

1.8

10.3S / 10.3

-

6.5 / 0

2.25"

500 Nat

CG10

On/Off

499

1.7

10.3S / 10.3

-

5.5 / 0

2.25"