beautypg.com

Bryant 588A User Manual

Page 20

background image

ELECTRICAL DATA

UNIT
588A

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

COND.

FAN

MOTOR

INDOOR

FAN

POWER SUPPLY

AWG 60 C

MIN WIRE

SIZE

MAX WIRE

LENGTH

(ft)

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

018

208/230-1-60

187

253

7.6

45

0.7

1.8

12.0

15

14

75

024

208/230-1-60

187

253

12.4

61

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82

1.4

2.0

21.8

30

10

100

208/230-3-60

187

253

9.4

66

1.4

2.0

15.5

25

12

80

036

208/230-1-60

187

253

18.0

96

1.4

2.8

26.7

40

10

90

208/230-3-60

187

253

11.7

75

1.4

2.8

18.8

30

12

65

460-3-60

414

506

5.6

40

0.8

1.4

9.2

10

14

100

042

208/230-1-60

187

253

20.4

104

1.4

4.0

30.9

50

8

100

208/230-3-60

187

253

14.0

91

1.4

4.0

22.9

35

10

85

460-3-60

414

506

6.4

42

0.8

2.0

10.8

15

14

100

048

208/230-1-60

187

253

26.4

129

2.1

5.0

40.1

60

6

100

208/230-3-60

187

253

15.0

99

2.1

5.0

25.9

40

10

75

460-3-60

414

506

8.2

50

1.1

2.3

13.7

20

14

100

060

208/230-1-60

187

253

32.1

169

2.1

6.8

49.0

60

6

100

208/230-3-60

187

253

19.3

123

2.1

6.8

33.0

50

8

90

460-3-60

414

506

10.0

62

1.1

3.2

16.8

25

12

100

LEGEND

AWG

American Wire Gage

CSA

Canadian Standards Association

FLA

Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration
LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (fuses or HACR-type

circuit breaker)

NEC

National Electrical Code

RLA

Rated Load Amps

*Fuse or HACR breaker.
†Minimum wire size is based on 60 C copper wire. If other than 60 C is

used, determine size from NEC. Voltage drop of wire must be less than
2% of rated voltage.

NOTES:
1. In compliance with NEC requirements for multimotor and combination

load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker. The CSA
units may be fuse or circuit breaker.

2. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

20