Bryant 588A User Manual

Page 15

background image

NET COOLING CAPACITIES (cont)

588A036 (3 TONS)

Indoor

Coil Air

Outdoor Coil Entering-Air Temperature (F)

85

95

105

115

Cfm

BF

Ewb

(F)

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

1050

0.07

72

41.7

19.9

3.99

39.3

19.1

4.18

37.2

18.4

4.39

34.7

17.5

4.57

67

37.6

25.4

3.86

35.5

24.7

4.05

33.2

23.8

4.23

30.9

22.9

4.41

62

33.6

30.5

3.72

31.2

29.4

3.90

28.8

28.2

4.08

26.7

26.7

4.26

1200

0.08

72

42.3

20.7

4.08

40.2

20.1

4.29

37.6

19.2

4.48

35.0

18.3

4.66

67

38.3

27.1

3.95

36.0

26.2

4.14

33.7

25.4

4.32

31.3

24.5

4.50

62

34.2

32.5

3.81

31.9

31.4

3.99

30.0

30.0

4.17

28.1

28.1

4.37

1350

0.09

72

42.6

21.4

4.15

40.4

20.8

4.36

37.9

20.0

4.56

35.2

19.0

4.73

67

38.7

28.5

4.03

36.4

27.7

4.22

34.0

26.8

4.41

31.6

25.9

4.58

62

34.8

34.2

3.90

32.8

32.8

4.09

31.1

31.0

4.29

29.2

29.2

4.48

588A042 (3

1

2

TONS)

Indoor

Coil Air

Outdoor Coil Entering-Air Temperature (F)

85

95

105

115

Cfm

BF

Ewb

(F)

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

1225

0.11

72

47.9

23.5

4.57

45.3

22.5

4.81

43.0

21.8

5.08

40.1

20.7

5.30

67

44.2

30.0

4.43

41.8

29.2

4.67

39.3

28.2

4.90

36.7

27.2

5.12

62

40.3

36.1

4.28

38.0

34.9

4.50

35.7

33.8

4.73

33.3

32.5

4.94

1400

0.12

72

48.5

24.3

4.66

45.9

23.4

4.91

43.3

22.5

5.17

40.4

21.4

5.39

67

44.9

31.7

4.52

42.5

30.9

4.77

39.9

29.9

5.01

37.2

28.8

5.23

62

41.1

38.3

4.38

38.8

37.1

4.61

36.4

35.8

4.84

34.1

34.1

5.06

1575

0.14

72

49.0

25.0

4.75

46.4

24.2

5.00

43.7

23.4

5.26

40.8

22.3

5.49

67

45.4

33.2

4.61

43.0

32.5

4.87

40.4

31.5

5.10

37.6

30.4

5.32

62

41.8

40.2

4.48

39.4

38.9

4.71

37.2

37.2

4.94

35.0

35.0

5.18

588A048 (4 TONS)

Indoor

Coil Air

Outdoor Coil Entering-Air Temperature (F)

85

95

105

115

Cfm

BF

Ewb

(F)

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Capacity

(Btuh x 1000)

Total

System

kW

Total

Sensible

Total

Sensible

Total

Sensible

Total

Sensible

1400

0.08

72

52.9

25.6

4.95

50.9

24.8

5.38

48.8

24.1

5.83

46.4

23.4

6.34

67

48.3

32.7

4.85

46.4

32.1

5.28

44.2

31.2

5.73

41.5

30.2

6.22

62

43.8

39.4

4.76

41.9

38.6

5.17

39.3

37.3

5.61

36.6

35.9

6.08

1600

0.10

72

53.7

26.4

5.07

51.7

25.9

5.50

49.2

25.1

5.95

47.0

24.3

6.45

67

49.1

34.6

4.97

47.0

33.9

5.40

44.7

33.1

5.85

42.4

32.4

6.34

62

44.5

41.9

4.87

42.6

41.1

5.29

40.1

39.7

5.74

37.7

37.6

6.22

1800

0.11

72

53.9

27.1

5.17

52.2

26.8

5.61

49.6

26.0

6.06

47.4

25.4

6.57

67

49.6

36.4

5.08

47.5

35.9

5.51

45.2

35.1

5.96

42.8

34.2

6.46

62

45.1

44.1

4.99

43.3

43.1

5.41

41.2

41.2

5.87

39.0

39.0

6.36

LEGEND

BF

Bypass Factor

Edb

Entering Dry-Bulb

Ewb — Entering Wet-Bulb
Ldb

Leaving Dry-Bulb

Lwb — Leaving Wet-Bulb
SHC — Sensible Heat Capacity (1000 Btuh)

NOTES:
1. Ratings are net; they account for the effects of the indoor-fan motor

power and heat.

2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:

sensible capacity (Btuh x 1000)

t

= t

ldb

edb

1.10 x cfm

t

= Wet-bulb temperature corresponding to enthalpy of air

lwb

leaving indoor coil (h

)

lwb

total capacity (Btuh x 1000)

h

= h

lwb

ewb

4.5 x cfm

Where: h

= Enthalpy of air entering indoor coil

ewb

4. The SHC is based on 80 F edb temperature of air entering indoor

coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

15