I/O Power Supply Modules (T3510, 11, and 12)
P D - 6 0 0 8 M a r - 0 6
7
not meet the DIN VDE 0110 specification for creepage and
clearance required by TÜV.
Specifications
Available Load Units
Number of I/O Units:
Load Unit Capacity:
1
2
3
4
52
48
44
40
Voltage Range
T3510
T3511
T3512
85 to 132 VAC
170 to 263 VAC
20 to 30 VDC
Frequency Range
T3510
T3511
T3512
47 to 63 Hz
47 to 63 Hz
—
Maximum Load
250 VA, per module
Heat Dissipation
22 Watts, 75 BTUs/hour
Use with Chassis
T3510
T3511
T3512
T3500
T3501
T3502
Fusing (on chassis)
T3510 (110 VAC)
T3511 (220 VAC)
T3512 (24 VDC)
4A, 250 V, 3AG Slow Blow
2A, 250 V, 3AG Slow Blow
10 A, 250 V, 3AB Slow Blow
Output Voltage
+15 volts
Power Hold-up Time
10 msec, minimum
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Vibration
10 to 55 Hz:
±0.15mm