Rockwell Automation T3512 ICS Regent Power Supply Modules User Manual
Ics regent, I/o power supply modules, Module operation
ICS Regent
®
PD-6008
Industrial Control Services
1
I/O Power Supply Modules
110 VAC, 220/240 VAC and 24 VDC
(T3510, T3511 and T3512)
Issue 1, March, 06
I/O power supply modules convert main line voltages of either
110 VAC, 220/240 VAC or 24 VDC to +15 VDC power that is
used to drive the I/O assembly (I/O chassis, I/O modules, and
I/O transceivers).
Three I/O power supply modules installed in an I/O power
supply chassis make up a triple redundant power supply unit.
Features
·
Three modules provide triplicated power to as many as four
I/O assemblies.
·
Hot replaceable.
·
Front panel indicator on each module shows DC output
status.
·
TÜV certified for safety, Risk Class 5 (see Safety
Considerations).
Failed I/O power supply modules can be hot replaced without
interrupting system operation.
Module Operation
Triplicated Power Distribution
Each of the triple redundant I/O power supply modules within
the I/O power supply assembly provides power for one leg of
the three redundant legs of the I/O Safetybus transceivers,
and provides power to all the I/O modules within its associated
I/O chassis. Each I/O module contains a diode OR power-