Rockwell Automation Publication PFLEX-UM003B-EN-P - July 2012

Installation and Wiring

DriveGuard Safe Torque Off Option Terminal Description

Verify Operation

Test the safety function for proper operation after the initial installation of
the DriveGuard Safe Torque Off option. Retest the safety function at the
intervals determined by the safety analysis described on

page 10

.

Verify that both safety channels are functioning according to the Table 4 or
Table 5.

No.

Signal

Description

1

Monitor - N.C. Normally closed contacts for monitoring

relay status.
Maximum Resistive Load:

250V AC / 30V DC / 50 VA / 60 Watts
Maximum Inductive Load:

250V AC / 30V DC / 25 VA / 30 Watts

2

Common - N.C.

3

+24V DC

Connections for user supplied power to

energize coil.
33.3 mA typical, 55 mA maximum.

4

24V Common

1

2

3

4