Cabinet Mounting, Wire Routing, and Liquid-Cooling Connections
3-1
C
HAPTER
3
Cabinet Mounting, Wire Routing,
and Liquid-Cooling Connections
This chapter provides cabinet dimension information that must be considered when
installing a Trane cabinet. It describes how to mount the Trane cabinet and shows
where the wire entry areas and liquid-cooling connection points are located.
3.1
Planning the Cabinet Installation
Cabinet dimensions and weights are listed in table 3.1. Overall cabinet dimensions are
illustrated in figure 3.1. Cabinet mounting holes are shown in figure 3.2.
Be sure there is adequate clearance for air ventilation around the cabinet. Allow a
minimum clearance of 1 foot per side. Allow 4 feet of clearance for the door to open.
3.2
Mounting the Cabinet
Attach the cabinet to the CenTraVac
chiller using the 8 mounting holes provided. In
order to maintain a flat mounting surface and to ensure that screw tightness is
maintained, use a washer and lock washer under the screw heads. Refer to figure 3.1
and table 3.1 for cabinet mounting dimensions. Use 3/8” (upper) and 1/2” (lower)
mounting screws and washers to attach the cabinet to the chiller. See figure 3.2 and
table 3.2 for mounting hole locations and dimensions.
Table 3.1 – Cabinet Dimensions
Dim. A
Dim. B
Dim. C
Dim. D
Dim. E
Dim. F
Weight
965 mm
38.0"
1524 mm
60.0"
379 mm
15.1"
1608 mm
63.3"
60 mm
2.4"
23 mm
0.91"
440 kg
970 lbs
Table 3.2 – Cabinet Mounting Hole Dimensions
Dim. A
Dim. B
Dim. C
Dim. D
Dim. E
Dim. F
Dim. G
1268.4mm
49.94"
85.7mm
3.38"
114.3mm
4.5"
314.3mm
12.38"
127.0mm
5.0"
254.0mm
10.0"
660.4mm
26.0"