Regulation Mode

Selection

The FlexPak Plus Drive has three

modes of regulation; A = Speed

Regulation by Armature Voltage, T

= Speed Regulation by Tachometer

or C = Counter EMF Feedback.
This initial SetĆup Procedure will be

conducted in the Armature Voltage

Mode with the selection jumper set

on pin A on the Regulator Board

even though a tachometer may be

used in the final system

configuration. Refer to Figure 4Ć2

and set the Regulation Mode

jumper to the A position.

Power On

Once all the preliminary checks

have been completed, apply AĆC

Power to the Drive. Carefully

observe all cautions and warnings.

DANGER

THE FOLLOWING CHECKS

AND PROCEDURES REQUIRE

THE POWER TO BE ON.

EXERCISE EXTREME CARE

AS HAZARDOUS VOLTAGE

EXISTS.

FAILURE TO OBĆ

SERVE THIS PRECAUTION

COULD RESULT IN SEVERE

BODILY INJURY OR LOSS OF

LIFE.

WARNING

FOR DRIVES WITH A FIELD

SUPPLY KIT, IF THE CIRCUIT

BREAKER HAS TRIPPED OR

THE POWER FUSES HAVE

BLOWN, THE FIELD SUPPLY

KIT AND ITS WIRING MUST BE

INSPECTED FOR DAMAGE.

AFTER REĆAPPLYING POWER

TO THE DRIVE, THE FIELD

VOLTAGE

MUST

BE

CHECKED

FOR

PROPER

VOLTAGE AT MOTOR TERMIĆ

NALS F1 AND F2. IF THIS

VOLTAGE IS BELOW 90% OF

THE SPECIFICATION VOLTĆ

AGE, THE DRIVE MUST NOT

BE STARTED UNTIL PROPER

VOLTAGE IS OBTAINED. FAILĆ

URE TO OBSERVE THIS PREĆ

CAUTION COULD RESULT IN

BODILY INJURY.

Verify that the F1 - F2 Field Supply

Voltage is the same as the motor

nameplate voltage if the Field

Supply Kit is used.
Check and verify control power

voltages before proceeding. See

Table 4Ć2 for nominal values.