3: Install and Wire The Drive
DANGER
ONLY QUALIFIED ELECTRIĆ
CAL PERSONNEL FAMILIAR
WITH THE CONSTRUCTION
AND OPERATION OF THIS
EQUIPMENT AND THE HAZĆ
ARDS INVOLVED SHOULD
INSTALL, ADJUST, OPERATE
AND/OR
SERVICE
THIS
EQUIPMENT.
READ AND
UNDERSTAND THIS MANUAL
IN ITS ENTIRETY BEFORE
PROCEEDING. FAILURE TO
OBSERVE THIS PRECAUTION
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
DANGER
THE USER IS RESPONSIBLE
FOR CONFORMING TO THE
NATIONAL
ELECTRICAL
CODE (NEC) AND ALL OTHER
APPLICABLE LOCAL CODES
WITH RESPECT TO WIRING
PRACTICES,
GROUNDING,
DISCONNECTS, AND OVERĆ
CURRENT PROTECTION ARE
OF
PARTICULAR
IMPORĆ
TANCE.
FAILURE TO OBĆ
SERVE THIS PRECAUTION
COULD RESULT IN SEVERE
BODILY INJURY OR LOSS OF
LIFE.
DANGER
THIS EQUIPMENT IS AT LINE
VOLTAGE WHEN AĆC POWER
IS CONNECTED. DISCONĆ
NECT AND LOCKOUT ALL
UNGROUNDED
CONDUCĆ
TORS OF THE AĆC POWER
LINE. FAILURE TO OBSERVE
THIS PRECAUTION COULD
RESULT IN SEVERE BODILY
INJURY OR LOSS OF LIFE.
General
This Section outlines the
procedures that are to be followed
to properly install the FlexPak Plus
SingleĆPhase DĆC Drive. Refer to
Figure 3Ć2 for mounting dimensions.
Install the Controller -
Panel Layout
The controller is designed as a
panel mount unit and must be hung
within 10_ of vertical with the rear of
the chassis firmly bolted to the
mounting surface. Do not mount the
chassis in a horizontal position.
Leave 2 inches (50 mm) clearance
between the top of one Drive and
the bottom of another Drive. This
area must remain unobstructed for
proper air circulation through the
heat sink. Do not place the
controller directly in a corner, leave
at least 8 inches (200 mm) from the
top and 6 inches (150 mm) from the
bottom of the cabinet.
Regardless of the above placement
guidelines, the user is responsible
for ensuring that the Controller's
ambient specification of 0 to 55_C i s
met. Relative humidity must be kept
within 5% to 95% without
condensation.
8 i n.
(200 mm
)
2 i n.
(50 mm
)
6 i n.
(150 mm
)
Figure 3.1 - Enclosure Mounting
Minimum Distances