Rockwell Automation T3470A ICS Regent Analogue Output Modules User Manual

Ics regent, Analog output modules, Module operation

background image

ICS Regent

®

PD-6025

Industrial Control Services

1

Analog Output Modules

4 to 20 mA

(T3470A)

Issue 1, March, 06

Analog output modules provide 4 to 20 mA current outputs for
a maximum of eight user loads per module. The module's
triplicated I/O Safetybus interface ensures that no Regent
system failure will inadvertently affect the output signal, and
that no failure in the module can affect the operation of the
Regent system or other I/O modules in the system.

Features

·

Eight 4 to 20 mA output circuits.

·

High resolution 12-bit D/A converter per output.

·

Hot-replaceable.

·

Automatic testing of triplicate I/O Safetybus circuits and many

simplex logic circuits.

·

Front panel indicators on each module show active/fault and

shutdown status.

·

2500 volt minimum electrical isolation between field and logic

circuits.

·

TÜV certified, Risk Class 5, non-interfering.

Module Operation

A block diagram of the analog output module is shown in
Figure 1.

The processor modules send triplicated write data commands
to the output module over the I/O Safetybus. The processors’
addressing data and data write commands are voted by the
module (preventing I/O Safetybus failures upstream from the