Serial Converter Parameters

B-5

Number of duplicate messages sent by the serial converter. This
value contains the total number of consecutive messages received
by this device with the same TNS (Transaction Sequence) number.

Auto: Converter will automatically run DPI if connected to a DPI
product.

Data rate used by the DPI host product. This data rate is set in the
drive, and the adapter autobauds to it.

DF1 address actually used by the serial converter.

1

This value is normally a low value. If it is continually incrementiong and you

are having communications problems, use a lower baud rate or replace the
RECBL-SFC serial cable.

15

Duplicate Msgs

1

Range:

0 to 65535

Default:

0

Type:

Read Only

16

(Reserved)

Range:

0 = Auto

Default:

0

Type:

Read/Write

17

DPI Data Rate

Range:

0 = 125 kbps
1 = 500 kbps

Default:

1

Type:

Read Only

18

DFI Addr Actual

Range:

0 to 254

Default:

0

Type:

Read Only