I/o companion slot cable type tc-215, Figure 13 i/o companion slot cable type tc-215, Trusted – Rockwell Automation TC200 Trusted I/O Companion Slot Cables User Manual
Page 21: I/o companion slot cables tc-200
![background image](/manuals/581454/21/background.png)
Trusted
TM
I/O Companion Slot Cables TC-200
Issue 14 Apr 10
PD-TC200
21
13. I/O Companion Slot Cable Type TC-215
This type of cable, and the modules/field termination assemblies it is used with, is shown in Figure 13
Figure 13 I/O Companion Slot Cable Type TC-215
This type of Trusted
TM
I/O Companion Slot Cable is designed for use with 24V or 120V dc digital output
modules and is suitable for connecting output signals from the module to an internal FTA. Power
connections are integral with this type of cable.
The chassis end of the multi-core cable is fitted with two 96-way type ‘C’ connectors housed in a
double-width hood. The other end of the cable is fitted with a 96-way type ‘R’ connector housed in a
single-width hood enabling the cable to be connected to an FTA.
Using this cable, the field power is connected at the FTA, which has indicators for each power group
which are voltage sensitive. For this reason, the T8850 FTA should be used with the T8451 and the
T8870 with the T8471.
The 0V connection at the FTA end allows a module reference so that it can measure its output voltage,
this must be connected to the field 0 Volts.
The FTA contains isolated power group field 0 Volts which connect to field 0V supply. Commoning of
the reference is obtained by a connection to this field supply.
The multi-core cable is stripped back 1.5m at both ends, then shrouded in nylon Rilgain sheathing.
The ends of the sheathing are heated or fitted with over sleeving to prevent fraying.
At both the chassis and remote end, a sheathed braid allows the connector hood to be wired to safety
earth. At the remote end, the multicore screen drain is wired to a green wire to allow connection to
screen earth.
Module
T8451
T8471
T8461
T8480
FTA
T8850
T8870