beautypg.com

Rockwell Automation 440R MSR241 Minotaur Safety Relay User Manual

Page 3

background image

MSR241 DeviceNet for Safety System MSR200

3

______________________________________________________________

Communicate with the MSR241 module



To transfer data from MSR241 to the D-Net it is required to upload the
Electronic Data Sheet” (EDS file). This file is available for free download on
the A-B web-page:

http://www.ab.com/networks/eds/

>Product Name

MSR241P

The name of the EDS file is: 0001000C00A30100.eds

The MSR241 operates as a “Group 2 only slave” device and supports UCMM.

The MSR241 is exchanged with the master through a polled, cyclic or change
of state connection.

Polled – Masters initiates communication by sending its polled I/O messages
to the MSR241 module. The module consumes the message, updates any
outputs, and produces a response. The response contains the input data.

Cyclic – allows configuration of the module as an I/O client. The module will
produce and consume its I/O cyclically at the rate configured.

Change of state – production occurs when an input changes. If no input
change occurs within the expected packet time, a heartbeat production
occurs. This heartbeat production tells the scanner module that the MSR241
is alive and ready to communicate. Consumption occurs when data changes
and the master produces new output data to the module.

The module produces 4 bytes and consumes 1 byte for outputs.