Rockwell Automation 20D Lifting Mounting PowerFlex 700S and 700H Drives (Frame 10 - 14) User Manual
Page 3

Lifting & Mounting PowerFlex® 700S and 700H Drives (Frames 10 - 14)
3
Step 1: Attaching the
Lifting Hardware to the
Drive
Directions for Drives Installed in Standard Rittal Enclosures
Table 1 Frames 10 - 13 Approximate Drive and Enclosure Weights
A
A
Min. 60°
B > A
C
B
TIP: To ensure that this angle is
greater than 60°, make the length
of chain or cable between the
center and the corners (B) longer
than the distance between the
opposite corners (A).
OR
Note: Lift each Frame 14 drive enclosure section
separately. Refer to
for more information.
Frame
Size
Voltage
Class
Drive
Rating
Amps
AC Input Drive & Enclosure
Weight -
kg (lbs.)
AC Input Drive,
Enclosure & Packaging
Weight - kg (lbs.)
DC Input Drive &
Enclosure Weight -
kg (lbs.)
DC Input Drive,
Enclosure & Packaging
Weight - kg (lbs.)
10
400
385
382 (842)
432 (952)
267 (589)
317 (699)
460
382 (842)
432 (952)
267 (589)
317 (699)
520
382 (842)
432 (952)
267 (589)
317 (699)
600
261
320 (705)
370 (816)
267 (589)
317 (699)
325
351 (774)
401 (884)
267 (589)
317 (699)
385
351 (774)
401 (884)
267 (589)
317 (699)
416
351 (774)
401 (884)
267 (589)
317 (699)
11
400
590
564 (1243)
614 (1354)
396 (873)
446 (983)
650
564 (1243)
614 (1354)
396 (873)
446 (983)
730
564 (1243)
614 (1354)
396 (873)
446 (983)
600
460
511 (1127)
561 (1237)
396 (873)
446 (983)
502
511 (1127)
561 (1237)
396 (873)
446 (983)
590
626 (1380)
676 (1490)
396 (873)
446 (983)
12
400
820
814 (1795)
864 (1905)
584 (1287)
634 (1398)
920
814 (1795)
864 (1905)
584 (1287)
634 (1398)
1030
814 (1795)
864 (1905)
584 (1287)
634 (1398)
600
650
752 (1658)
802 (1768)
584 (1287)
634 (1398)
750
752 (1658)
802 (1768)
584 (1287)
634 (1398)
820
752 (1658)
802 (1768)
584 (1287)
634 (1398)