Pre-charge connections on drives with dc input – Rockwell Automation 20D PowerFlex 700H/S Frame 11 Replacement Power Structure User Manual
Page 14
14
PowerFlex® 700S and 700H Frame 11 Replacement Power Structures
Pre-Charge Connections on Drives with DC Input
You must connect the ASIC board connectors X9 and X15 to the X50
terminal block for the pre-charge circuit. The X50 terminal block is located
on the Control Frame. Refer to the Installation Instructions - PowerFlex
700S and 700H High Power Drives, publication PFLEX-IN006
…,
for
information regarding the pre-charge circuit.
X50 Terminal Block Connections
Figure 9 Sample Pre-charge Wiring Diagram
ASIC Board Charge Relay Contact Ratings
ASIC Board
Connector
Terminal
to
X50 Terminal Pre-Charge Circuit Connection Description
X9
25
. . .
1
Pre-charge Complete Signal (+24V DC)
26
. . .
2
Pre-charge Complete Signal (Common)
X15
21
. . .
3
Charge Relay Contact
23
. . .
4
Charge Relay Contact
M
F2
R2 CR2
DC+
DC Source
DC-
CR2
R1
F1
M
Customer Connections - External precharge
circuitry is shown as dashed lines.
Drive Connections
Terminal Block
CR1
Pilot Relay
CR1
M
Main DC Contactor
M
CR2
Precharge
M
Precharge
Complete
1
2
3
4
25
26
21
23
X15
X9
ASIC Board
X50
Charge
Relay*
*Refer to the “ASIC Board
Charge Relay Contact
Ratings” table below.
Important: For DC Input Only.
Do Not Install on AC Input Drives
Load
Resistance load (cos
φ
= 1)
Rated load
8 A at 250 VAC: 5 A at 30 VDC
Rated carry current
8 A
Max. switching voltage
250 VAC; 30 VDC, (400 VAC)
Max. switching current
AC 8 A; DC 5 A
Max. switching power
2,000 VA; 150 W
Failure rate (reference value)
5 VDC 10 mA (for gold plating 0.35 µ min.)