Wiring diagram, At rear of fuse holder – Rockwell Automation Flex/WebPak 3000 Digital DC Drive Blower Motor Starter Kit User Manual
Page 4
![background image](/manuals/581180/4/background.png)
4
Blower Motor Starter Kits for FlexPak 3000 and WebPak 3000 Digital DC Drives
Step 5. Turn the overload relay potentiometer to the blower motor’s rated full load current. Set the overload
relay to A (Auto). See figure 1 or figure 5.
Step 6. Connect the blower motor leads to the blower motor starter’s T1, T2, and T3 terminals.
Step 7. Turn on power to the drive.
Step 8. Check for proper blower motor rotation. If the blower motor is rotating in the wrong direction;
a.
Turn off, lockout, and tag power to the drive.
b.
Swap the blower motor leads connected to the blower motor starter’s T1 and T2 terminals.
c.
Turn on power to the drive.
d.
Repeat the check for proper blower motor rotation.
Step 9. Turn off and lockout power to the drive.
Step 10. Install the cover on the drive or drive's line fuse panel, if necessary.
Step 11. Turn on power to the drive.
Kit installation is now complete.
Figure 1 – Typical Blower Motor Starter (1.5 HP to 300 HP Drives)
1 3
5
3
1
1 4
2
A 12
9 5
96
9 8
9 7
T3
T2
T1
T E
S T
T R
IP
P E
D
4
6
13FU 14FU 15FU
182
183
181
At rear of fuse holder
Wiring Diagram
183/L3
182/L2
181/L1
P8-3
P8-4
P8-2
P8-1
OL
N
OL
N
2
4
6
OL
SUP
N
A2
A1
OL
OL
95
96
98
97
N AUX
14
13
T1
1
15FU
14FU
3
T2
N
T3
5
13FU
P8 Connector
Set to "A"
(AUTO)
Set to rated blower
motor amps (FLA)