Checking the contents of the kit, Installation – Rockwell Automation Flex/WebPak 3000 Digital DC Drive Blower Motor Starter Kit User Manual
Page 2

2
Blower Motor Starter Kits for FlexPak 3000 and WebPak 3000 Digital DC Drives
Checking the Contents of the Kit
Verify the contents of the kit. Each kit consists of the following:
Important: Drives rated at 400 HP to 600 HP @ 460 VAC may require 2 identical blower motor starter kits.
Important: Replacement in-line fuses are not supplied with the kit. See table 2 for the correct replacement
fuse rating and part number.
Installation
Important: The following procedures assume the drive is wired and operational. See your FlexPak 3000 or
WebPak 3000 hardware instruction manual for more information.
Mounting the Blower Motor Starter on the Drive Chassis
Make sure you are referring to the correct figures when installing your blower motor starter kit.
Description
Qty
Prewired starter assembly on a mounting bracket (blower motor starter, controls, fuse block,
installed fuses, short wire harness)
1
Long wire harness
1
Wire ties
2
Table 2 – Blower Motor Starter Kit Replacement Fuses
For Kit Model Number:
Order Reliance Fuse Part Number:
Fuse Amperage
902FK0101
64676-72C
0.8
902FK0201
64676-72E
1.25
902FK0301
64676-72H
2.0
902FK0401
64676-73J
2.5
902FK0501
64676-73L
3.5
902FK0601
64676-73N
4.5
902FK0701
64676-73R
6.0
902FK0801
64676-73U
7.5
902FK0901
64676-73W
9.0
902FK0111
64676-73Y
12.0
902FK0121
64676-73Z
15.0
!
ATTENTION: Do not install modification kits with power applied to the drive. Disconnect and lock
out incoming power before attempting such installation. Failure to observe this precaution could
result in severe bodily injury or loss of life.
Drive
See figures
1.5 HP to 30 HP @ 230 VAC / 3 HP to 60 HP @ 460 VAC
1 and 2
40 HP to 75 HP @ 230 VAC / 75 HP to 150 HP @ 460 VAC
1 and 3
100 HP to 150 HP @ 230 VAC / 200 HP to 300 HP @ 460 VAC
1 and 4
400 HP to 600 HP @ 460 VAC
5 and 6