beautypg.com

Technical description – Rockwell Automation MAO04NND Analogue Output Module User Manual

Page 7

background image

MAO04NND October 2005 – Issue 1

7

Triguard SC300E MAO04NND Analogue Output Module

TECHNICAL DESCRIPTION

PHYSICAL

The MAO04NND is a 9U high PCB with integral front panel and rear connectors. A plug-in
daughterboard carries the common interface circuits. Figure 1-1shows the general layout,
including the location of the connectors, covers and configuration links.

The front panel provides the following: Three ‘On-Line’ indicators A ‘Health’ indicator

An On/Off line request switch

Five test jacks (4 line and a common) for monitoring the output lines.

NOTE

Each monitor point gives 0 to 5.5Vdc negative with respect to common, determining the current
flowing in the corresponding 0 to 22 mA output. Each monitor point has a 10k ohm resistance
in series to prevent malfunction if the monitor point is short circuited - so a high input-
resistance meter is required for accurate readings.

MECHANICAL CODING BLOCKS

All Input/Output modules carry two mechanical coding blocks equipped with pins which mate
with holes in corresponding blocks in the chassis and prevent the module being inserted into
the wrong slot. The pins in the module blocks are factory installed in a pattern determined by
the module and corresponding set screws are removed from the chassis coding blocks to
enable fitting. Unused holes are plugged with set screws. The chassis coding block
configuration for this module is shown in Figure 2-1 .

Figure 2-1 Chassis mechanical coding block configurations