beautypg.com

Rockwell Automation MAO04NND Analogue Output Module User Manual

Page 4

background image

4

MAO04NND Octrober 2005 – Issue 1

Triguard SC300E

SPECIFICATION

Model

MAO04NND

Channels

4

Architecutre

TMR

Indicators

Health, 3 x On Line

Test points

4 x signal, 1 x common

Output range

0 to 22mA

Maximum resistive field load

400 ohm

Resolution

6.25

µA steps

Accuracy @ 25

°

C

+

0.2% of full signal range

Maximum input ripple voltage @ 24V field supply

12V peak to peak

Maximum input frequency

120HZ

Stability (temperature coefficient)

15ppm/

°

C

Isolation

1KV between field and system, commoned
supply

Field power supply

Volgate range

+18Vdc to 30Vdc

Module power consumption

5.5W

Overall size (mm)
Overall size (inches)

400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W

Weight

1.4kg

ENVIRONMENTAL SPECIFICATIONS

The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.

Temperature operating:

+5°C to +60°C

Temperature storage:

-25°C to +70°C

Humidity

5% to 95% non-condensing at ambient <40°C

EMC/RFI Immunity

Tested and certified to IEC 1131-Part 2 1994

Vibration/Shock

Tested and certified to IEC 1131-Part 2 1994

Certification:

General Certification: Ref. SC300E TMR Product Guide (ref 008-5209).