1 field power module, 2 standard features – Rockwell Automation SD3100 DISTRIB PWR SYS SD3100 DC PWR MODULE User Manual
Page 11

Introduction
1-3
1.1
Field Power Module
The single-phase Field Power Module is integrally mounted within the SD3100 Power
Module to provide the motor field excitation. The Field Power Module is rated 15 or 60
amps at 230/460 VAC. The 15A unit is supplied as standard. The 60A unit is available
as an option.
The Field Power Module requires a separately-ordered, separately-mounted field
isolation transformer. The Field Power Module’s AC input lines are connected through
the isolation transformer to the L1 and L3 inputs of the SD3100. The 15A module
requires a step-down transformer rated up to 7.5kVA (application dependent). The
60A module requires a step-down transformer rated 7.5kVA to 25kVA (application
dependent). All systems operate on three-phase 50/60 Hz., 460 to 660 VAC.
The Field Power Module is available in the configurations listed in table 1.2.
1.2
Standard Features
SD3100 DC Power Modules have the following features:
•
Three-phase 460, 575, or 690 VAC input
•
1250, 1650, and 3000 amp units
•
S6 (non-regenerating) and S6R (regenerating) configurations
•
15 amp Field Power Module
•
DC output contactor
•
PE / TE bus
•
Choice of incoming circuit breaker or input line fuse protection
•
Electronic motor overload protection
•
SCR power semiconductors / dv/dt protection
•
SCR leg fuses
•
Cell chokes
•
Protection against unequal current sharing among SCRs
•
Protection from AC line dips and transients
•
Top AC entry / Bottom DC exit
•
Power through-bus (1250A and 1650A Power Modules)
Table 1.2 – Field Power Module Part Numbers
Part No.
Amps
AC Input
Description
Mounting
805405-3R
1
1. For application information see instruction manual S-3060.
15
230 / 460 VAC
Reversing (S2R)
Integral
805405-5R
1
60
230 / 460 VAC
Reversing (S2R)
Integral