0x5000 series codes (input field interface unit), Trusted – Rockwell Automation T80020 Application Note Diagnostic Procedures User Manual
Page 50
Trusted
TM
AN-T80020 Diagnostics Procedure
Issue 12 Feb 11
AN-T80020
50
0x5000 Series Codes (Input Field Interface Unit)
FIU_HFIU_RAM_FAIL
0x5000
Modules:Input, 8480
Detects serious errors in field interface/Host interface data transfer
RAM such as address/data faults. Return the module for repair.
Action:Slice OFFLINE
OFIU_FIA_SYNC_FAULT
0x500n
Subcode: n = quadrant (0 to 3)
Modules:8472, similar in 8442
Detects a failed OFIU quadrant (invalid FPGA configuration data,
power fault, logic fault, etc.) or an ISL synchronization fault. Return the
module for repair.
Action:Slice OFFLINE
FIU_HIA_SYNC_FAULT
0x5001
Modules:Input
Detects serious errors (or noise) in the FIU comms link such as a faulty
optocoupler, FIA, or FIU power supply. Return the module for repair.
Action:Slice OFFLINE
FIU_FIA_SYNC_FAULT
(input modules)
0x5002
Modules:Input
Detects noise in the IFIU comms link, also in the HIA and FIA. Return
the module for repair.
Action:Slice OFFLINE
FIU_FIA_SYNC_FAULT
(output modules)
0x5002
Modules:Output except
8472,8442
Detects serious errors (or noise) in the OFIU comms link such as a
faulty optocoupler or a dead output group. Return the module for
repair.
Action:Slice OFFLINE
FIU_REF_DRIFT
0x5004
Modules:Input
Checks internal reference channel 41 for drifting. This channel is used
to monitor the live channels. If the fault is persistent, return the module
for repair.
Action:Slice fault
OFIU_FIA_SYNC_FAULT
0x5004
Modules:8442,8472
This is similar to 500n above for 8472, but shows that all four quadrants
are faulty. This may be a slice fault, so the slice is set offline. Return
the module for repair.
Action:Slice OFFLINE
FIU_REF_OUTOFBOUNDS
0x5005
Modules:Input
Checks internal reference channel 41 for passing limits. This channel is
used to monitor the live channels. Return the module for repair.
Action:Slice OFFLINE
HSIU_RAM_TEST_FAULT
0x5005
Modules:8442
Detects any fault in free RAM. Return the module for repair.
Action:Slice OFFLINE
OFIU_IMON_BAL_FAULT
0x5005
Modules:8472
Checks for imbalance in output circuit current measurement. If the fault
is persistent, return the module for repair.
Action:Slice fault
IFIU_FREQ_FAULT
0x5006
Modules:Input
Checks the HIU and FIU logic that is used to control and generate the
FIU operating frequency. The operating frequencies are critical for
input channel fault detection. Return the module for repair.
Action:Slice OFFLINE