Rockwell Automation T3432-CA ICS Regent RTD Input Equipment User Manual
Page 26

RTD Input Equipment (T3432)
2 6
Industrial Control Services
Common Mode Rejection
100 dB @ 50/60 Hz
60 dB minimum, elsewhere
Normal Mode Rejection
70 dB typical
Termination Panel Cable
Length
Maximum 50 cable feet
(15 m)
Isolation
2500 volts minimum (Mux to
input module)
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity,
non-condensing
Safety
Pending certification to DIN
V VDE 0801 for Risk Class 5.
Also designed to meet UL
508 and CSA 22.2, No. 142-
M1981
Heat Dissipation
Input module:
Termination panel/Mux:
4.5 Watts, 15 BTUs/hour
2.5 Watts, 9 BTUs/hour
Dimensions
Input Module
Height:
Width:
Depth:
Termination Panel
Height:
Width:
Depth (with MUX):
12.6” (320 mm)
1.27” (32 mm)
10.125” (257 mm)
6.94” (176 mm)
19.0” (483 mm)
5.12” (130 mm)
Weight
Input module:
Mux:
Termination panel:
3.5 lbs (1.6 kg)
2 lbs (0.9 kg)
5.6 lbs (2.5 kg)