Rockwell Automation T3432-CA ICS Regent RTD Input Equipment User Manual
Ics regent, Rtd input equipment, Input module, mux, termination panel and cable
ICS Regent
®
PD-6037
Industrial Control Services
1
RTD Input Equipment
Input Module, Mux, Termination Panel and Cable
(T3432-IM, T3432-Mux, T3432-TP and T3432-CA)
Issue 1, March, 06
The RTD input equipment includes a RTD input module
(T3432-IM), a RTD input multiplexer (T3432-MUX), a RTD
termination panel (T3432-TP), and a RTD termination cable
(T3432-CA). This equipment provides terminations and
temperature conversion for as many as 16 RTD inputs,
arranged in 2 groups of eight inputs.
Features
·
Sixteen inputs for 100W platinum RTDs.
·
Configuration options:
RTD type:
American (a = 0.00392 W/W/° C)
European (a = 0.00385 W/W/° C)
Input Leads:
2, 3 or 4-wire
Units:
Degrees F or degrees C
Resolution:
Units or tenths
Noise Filter:
50 Hz, 60Hz rejection
·
Complete linearization and automatic calibration.
·
Remote terminations up to 50 cable feet from I/O chassis.
·
Individual front panel indicators on each module show active,
fault and MUX fault status.
·
2500 volt isolation between Input Module and Mux.
·
Hot-replaceable input module and Mux.
·
Extensive fault diagnostics.
·
TÜV certified for safety, Risk Class 5.
The input module plugs into an I/O chassis slot and receives
data from the RTD input multiplexer (or Mux). The RTD
input multiplexer plugs into the termination panel and
provides low level signal conditioning, multiplexing, and